Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
binary input and Modbus, provided the
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
binary input and Modbus, provided the
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
O
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
Mode 2 = Gen Start & Trip
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
-
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
-
reclose function can be used with any circuit breaker suitable for auto
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
Mode 2 = Gen Start & Trip
4:
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
-
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
Mode 2 = Gen Start & Trip
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
Mode 2 = Gen Start & Trip
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
tion of the auto reclosures function
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
Mode 2 = Gen Start & Trip
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
tion of the auto reclosures function
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
Mode 2 = Gen Start & Trip
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
tion of the auto reclosures function
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
Mode 2 = Gen Start & Trip
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
tion of the auto reclosures function
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
Mode 2 = Gen Start & Trip
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
tion of the auto reclosures function
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
Mode 2 = Gen Start & Trip
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
-
tion of the auto reclosures function
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosing. The function provides
There are two methods by which function can be initialized. The method to be used
Mode 2 = Gen Start & Trip
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
-
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
-
tion of the auto reclosures function
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
There are two methods by which function can be initialized. The method to be used
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
-
The function is initialized on rising
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
tion of the auto reclosures function
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
There are two methods by which function can be initialized. The method to be used
function is initialized on the rising edge of the external trip signal (received via
binary input and Modbus, provided the
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
, I>>>, Io>, Io>>, I2>, I2/I1>).
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
tion of the auto reclosures function
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
-
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
-
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
tion of the auto reclosures function
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
options for this settings are
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
tion of the auto reclosures function
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
options for this settings are
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
tion of the auto reclosures function
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
options for this settings are
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
O
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
options for this settings are
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
be registered as an event
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
-
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
options for this settings are
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
be registered as an event
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
options for this settings are
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
be registered as an event
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
options for this settings are
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
be registered as an event
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
options for this settings are
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
be registered as an event
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
options for this settings are
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
be registered as an event
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
reclosures of desired duration.
There are two methods by which function can be initialized. The method to be used
options for this settings are
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
be registered as an event
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
There are two methods by which function can be initialized. The method to be used
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
auto reclosure is not blocked AND circuit breaker is in ready condition (if
be registered as an event
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
energizing of the fault location for a
selected time period is implemented through automatic reclosing, during which
In case of a permanent fault, the automatic reclosing is followed by final tripping.
reclose function can be used with any circuit breaker suitable for auto
-
There are two methods by which function can be initialized. The method to be used
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
set via Activate t of receipt of general start signal (which will be an OR of start
However in addition it is required that circuit breaker is in closed position AND
be registered as an event
Protection and Control Function
Majority of overhead line faults are transients in nature and automatically cleared
In case of a permanent fault, the automatic reclosing is followed by final tripping.
There are two methods by which function can be initialized. The method to be used
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position
AND auto reclosure is not blocked AND circuit breaker is in ready condition (if
of the general trip signal (which will be
an OR of trip of I>, I>>, I>>>, Io>, Io>>, I2>, I2/I1>) if it is received within time
However in addition it is required that circuit breaker is in closed position AND
Protection and Control Function
There are two methods by which function can be initialized. The method to be used
function is initialized on the rising edge of the external trip signal (received via
However in addition it is required that circuit breaker is in closed position