EasyManuals Logo
Home>ABB>Protection Device>REJ601

ABB REJ601 User Manual

ABB REJ601
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
1MDU07212-YN Rev. C Section 5
Use of LHMI
REF601 / REJ601 51
Application Manual
5.2.8 Menu – Test
Submenu Test and respective submenus shows and allows depending on the user
right to perform several kind of tests to verify the IED functionality:
Test -> Hardware: Enables Internal Hardware Tests, which includes LCD check,
Keyboard check and LEDs check. User can skip particular checks using interactive
menu selection.
Test -> Binary Output (BO): Enables testing of all output contact to test the
complete external circuit initiated by the output contact. Once test BO selected
output will be operated for around 2 sec.
Test -> Functional: Enables each protection function tests by loading fixed analog
values for five seconds and ignoring actual analog inputs. User can test all
protection stages and accordingly its relay configuration by having a simulated
analog values for 5 seconds.
The details of functions available in test mode are described as under the respective
section.
Remark:
To modify settings needs user rights of Setting or Admin user.
Following menu structure is used to navigate to the respective test settings:
Figure 21: Test menu of relay REF601/REJ601 with its submenu

Table of Contents

Other manuals for ABB REJ601

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REJ601 and is the answer not in the manual?

ABB REJ601 Specifications

General IconGeneral
BrandABB
ModelREJ601
CategoryProtection Device
LanguageEnglish

Related product manuals