Trouble shooting
38 RHDE250 ... 4000 (Contrac) 42/68-167-EN
Pos: 19.1 /Überschri ften/1/A - F/Fehlerbehe bung @ 8\mod_117742145778 1_3101.doc @ 86174
8 Trouble shooting
Pos: 19.2 /Fehlermeldu ngen/Aktorik/An triebe/Allgemein/Fe hlersuche @ 10\mod_118 1571422531_3101.d oc @ 103198
This chapter only covers failures caused by the hardware. Use the online-help of the
configuration software for an extended troubleshooting.
failure pattern possible reason troubleshooting
actuator can not move the
valve
failure either at the
actuator or at the final
control element (e.g.,
stuffing box tightened too
much)
detach actuator from valve
if the actuator moves the valve is
the possible cause
if the actuator does not run, the
actuator is the possible cause
incorrect electronic unit or
incorrect data set
Compare the nameplate data on
the actuator and electronic unit.
Incorrectly configured
electronic unit
Check/update the settings for the
parametrization software
no communication with
the control system
Check wiring
incorrect wiring between
actuator and electronic unit
Check wiring
motor / brake faulty Check the winding resistance of
the motor and brakes
Check the brake lock
Binary inputs on the
electronic unit are not wired
Make connection
actuator does not react
Brake does not release
(no mechanical "click")
Check the brake air gap (approx.
0.25 mm) and electrical
connection to the brake
check winding resistance of the
brake coil
actuator does not run in AUT
mode, although “AUT” is
selected in the user interface
Binary input 1 (BE 1) not
wired
Make connection
Check the software settings for
the binary inputs
LEDs in the commissioning
and service panel (CSP)
flash synchronously
Actuator is not adjusted
properly
Adjust actuator
LEDs flash alternately Electronic unit / drive
failure
failure when approaching the
end position
Actuator in limit range of
positioning sensor
drive the actuator beyond the
adjusted end position (either
manually or using the push buttons
on the CSP); <:hr>(if necessary
disconnect from valve or damper)
drive the actuator back into the
operating range and connect it to
the valve / damper
re-adjust the operating range
os: 19.3 /Überschri ften/1.1/1-spaltig/ A - F/Elektrische Pr üfwerte @ 10\mod_1181642679 500_3101.doc @ 103909
8.1 Electrical test values
Pos: 19.4 /Fehlermeldu ngen/Aktorik/An triebe/RHDE250... 4000/Elektrisc he Prüfwerte @ 10\mod_11816316 42015_3101.doc @ 103346
BD 80 K-4B BD 80 L-4B BD 90 L2-4B BD 100 L2-4B
Winding resistance ± 5 % at 20 °C (68 °F)
motor 18,2 8,04 3,88 2,57
brake 910 910 648 575
Pos: 20 /======= Seitenumbruch ======== @ 0\mod_112 6532365768_3101.doc @ 3830

Table of Contents

Other manuals for ABB RHD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RHD Series and is the answer not in the manual?

ABB RHD Series Specifications

General IconGeneral
BrandABB
ModelRHD Series
CategoryController
LanguageEnglish

Related product manuals