Quick start-up guide
23
Parameter setting examples
Generic drives profile (PROFIdrive) with PPO Type 1 (DP-V0)
The RPBA-01 uses data-consistent communication, meaning that
the whole data frame is transmitted during a single program cycle.
Some PLCs handle this internally, but others must be
programmed to transmit data-consistent telegrams. For example,
Drive parameter Setting
ACS800 ACS550
10.01 EXT1 STRT/STP/DIR COMM.CW COMM
11.03 EXT REF1 SELECT COMM. REF COMM
16.01 RUN ENABLE COMM.CW COMM
16.04 FAULT RESET SEL COMM.CW COMM
98.02 COMM. MODULE LINK FIELDBUS –
98.02 COMM PROT SEL – EXT FBA
98.07 COMM PROFILE GENERIC –
51.01 MODULE TYPE PROFIBUS DP*
51.02 NODE ADDRESS 3
51.03 BAUDRATE 12000*
51.04 PPO-type PPO1*
51.21 DP MODE 0
51.27 FBA PAR REFRESH REFRESH
*Read-only or automatically detected