Quick start-up guide
23
Parameter setting examples
Generic drives profile (PROFIdrive) with PPO Type 1 (DP-V0)
The RPBA-01 uses data-consistent communication, meaning that
the whole data frame is transmitted during a single program cycle.
Some PLCs handle this internally, but others must be
programmed to transmit data-consistent telegrams. For example,
Drive parameter Setting
ACS800 ACS550
10.01 EXT1 STRT/STP/DIR COMM.CW COMM
11.03 EXT REF1 SELECT COMM. REF COMM
16.01 RUN ENABLE COMM.CW COMM
16.04 FAULT RESET SEL COMM.CW COMM
98.02 COMM. MODULE LINK FIELDBUS
98.02 COMM PROT SEL EXT FBA
98.07 COMM PROFILE GENERIC
51.01 MODULE TYPE PROFIBUS DP*
51.02 NODE ADDRESS 3
51.03 BAUDRATE 12000*
51.04 PPO-type PPO1*
51.21 DP MODE 0
51.27 FBA PAR REFRESH REFRESH
*Read-only or automatically detected