Measuring system:
Micro-processor system for
balanced three-phase networks or
single-phase networks.
Operating voltage:
220V to 240V, 380V to 440V
depending on type of PF Controller.
Voltage tolerance:
+/- 10% on indicated operating
voltages.
Frequency range:
50 or 60 Hz +/- 5% (automatic
adjustments to network frequency).
Current input:
5A (RMS).
Current input impedance:
<0.1 Ohm.
Consumption:
15 VA max.
Output contact rating:
• Max. continuous current: 1.5A.
• Max. peak current: 5A.
• Max. voltage: 440 Vac.
• Terminal A is rated for a
continuous current of 16A.
Alarm contact:
• Normally closed contact.
• Max. continuous current: 5A.
• Rated/max. breaking voltage:
250Vac/440Vac.
15. Technical Specifications
Power factor setting:
From 0.7 inductive to 0.7 capacitive.
Starting current setting (C/k):
• 0.05 to 1A.
• automatic measurement of C/k.
Number of outputs:
RVC 3: 3
RVC 6: 6
RVC 8: 8
RVC 10: 10
RVC 12: 12
Switching time between steps:
programmable from 1s to 999s
(independent of reactive load).
Saving-function:
All programmed parameters and
modes are saved in a non-volatile
memory.
Power outage release:
Automatic disconnection of all
capacitors in case of power outage
longer than 40ms.
Power outage reset delay time:
40s.
Autoadaptation to the phase-
rotation of the network and the
CT-terminals.
Insensitivity to harmonics.
Working with generative and
regenerative loads (four-quad-
rant operation).
LCD contrast automatically
compensated with temperature.
Operating temperature:
-10° C to 70° C.
Storage temperature:
- 30° C to 85° C.
Mounting position:
Vertical panel mounting.
Dimensions:
144x144x80 mm (hxwxd).
Weight:
0.8 kg (unpacked).
Connector:
WAGO.
Front plate protection:
IP 40.
Relative humidity:
Maximum 95%; non-condensing.
CE Marked.