15.2 PR120/D-M - COM communication module
15.2.1 General characteristics
Dedicated communication module for connecting the relay to a Modbus net, and for remote supervisory and control activities on the circuit-breakers.
15.2.2 Front view
- "Power" LED (lit when Vaux is installed)
- LED RX/TX (data send/receive signal).
15.2.3 Releases complete with the module
- optional for PR122/P
- optional for PR123/P
15.2.4 Power supply
The PR120/D-M - COM communication module is only powered by the relay if there is a 24V auxiliary voltage available.
15.2.5 Connection
Refer to fig. 45 in the wiring diagram provided in this manual.
15.2.6 Communication functions available
The communication function on the PR122/P, PR123/P releases with PR120/D-M - COM is listed in the table:
PR122/P or PR123/P + PR120/D-M - COM
Protocol Modbus RTU
Physical interface RS-485
Baud rate 9600 - 19200 bit/s
15.2.7 PR120/D-M - COM module menu
Parameter / Function Values Notes
Local/remote Local/remote
Serial address 1 ... 247 247 default address
Baudrate 9600 bit/s
19200 bit/s
Physical protocol 8,E,1 - 8,0,1 - 8,N,2 - 8,N,1
Addressing Modbus standard
ABB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Emax Series and is the answer not in the manual?

ABB SACE Emax Series Specifications

General IconGeneral
BrandABB
ModelSACE Emax Series
CategoryCircuit breakers
LanguageEnglish

Related product manuals