13.6.4 Error messages displayed in pop-up windows
All the messages that appear on the display in a pop-up window are described below.
Error message Description
Password error
Session impossible A programming session cannot be started due to a contingency (e.g. a timer-controlled delay still elapsing)
Value outside range Value beyond the established limits
Exception 6 Command temporarily unavailable
Unavailable Function temporarily unavailable
Invalid date Date has not been set
Parameters revised Programming session concluded correctly
Cancelled Programming session cancelled
Failed Programming session rejected
Failed 1001 Inconsistent thresholds of protections L and S
Failed 1002 Inconsistent thresholds of protections I and S
Failed 1009 Zone selectivity enabled in both protection S and G or Gext
Failed 3001 Inconsistency as to language change
Failed 3002 Inconsistency on Rc toroid
Failed 3003 Inconsistency as to external Neutral configuration
Configuration Parameters inconsistency
Configuration Relay key plug data inconsistency
Timing UV Timing protection UV
Timing OV Timing protection OV
Timing RV Timing protection RV
Timing RP Timing protection RP
Timing UF Timing protection UF
Timing OF Timing protection OF
Alarm message Description Notes