ABB | SACE Tmax XT
60 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A Protections | 5 - Power protections
5 - Power protections
Elenco
The Power protections, available by default for the Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch and Ekip M
Touch models and configurable in the remaining models as additional SW package, are:
Name Type of protection Page
RP Reverse active power 60
D
(2)
Directional short-circuit with adjustable delay 63
OQ
(1)
Maximum reactive power 63
OP
(1)
Maximum active power 63
UP
(1)
Minimum active power 64
RQ
(1)(2)
Reverse reactive power 64
Cos φ Minimum Cos φ 65
(1)
protection not available by default with Ekip Hi-Touch and Ekip M Touch. However, it can be integrated by
requesting the relative SW package
(2)
protection not available by default with Ekip G Touch. However, it can be integrated by requesting the relative
SW package
RP Protection
P11
t
t11
P
RP
Function
The protection sends a TRIP command if the reverse total active power exceeds threshold P11 for longer
than t1.
To check and simulate the trip times in relation to all the parameters, please consult:
summary table of the protections with the operating characteristics (page 80)
the graph with trip curve (page 92)
Parameters
Parameter Description Default
Enable
Activates/deactivates the protection and its availability in the parameters
menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Threshold f11
Establishes the value that activates the protection.
The value is given as both absolute value (kW) and relative value (Sn) and
can be set within the range: -0.05 Sn to -1 Sn in 0.001 Sn steps
NOTE: the threshold expressed in Sn is preceded by the “-” sign to
indicate that inverse power is involved
0,1 Sn
Time t11
This is the trip time of the protection; the value is given in seconds and
can be set within a range: 0.05 s to 120 s, in 0.01 s steps
10 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 75).

Table of Contents

Other manuals for ABB SACE Tmax XT5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Tmax XT5 and is the answer not in the manual?

ABB SACE Tmax XT5 Specifications

General IconGeneral
BrandABB
ModelSACE Tmax XT5
CategoryCircuit breakers
LanguageEnglish

Related product manuals