EasyManuals Logo
Home>ABB>Circuit breakers>SACE Tmax XT5

ABB SACE Tmax XT5 User Manual

ABB SACE Tmax XT5
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #198 background imageLoading...
Page #198 background image
ABB | SACE Tmax XT
196 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A Internal accessories | 9 - Ekip Maintenance
9 - Ekip Maintenance
Ekip Maintenance is a signaling accessory allowing a programmable input and a programmable output to be
managed.
The module can be configured in the CB according to standard UL; the menus and information about the
module are available in the Trip unit with the names of the respective module for the IEC standard (Ekip
Signalling 1K).
IMPORTANT: each circuit-breaker can house one module only; configuration with
external modules is not allowed if an internal module is present
Connections
The circuit diagrams and references concerning the terminals are available in document 1SDM000005A1001.
To connect the module to Ekip Touch and to actuator MOE-E if present, please consult document
1SDH002011A1507.
Power supply
Ekip Maintenance is supplied directly by the Ekip Touch to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Input
The input can be configured so that its status corresponds to actions or signals, with different programming
options (see Menu).
The module permits two logic statuses, interpreted differently by the Trip unit on the basis of the selected
configuration:
Parameter Description Contact configuration Status detected by Trip unit
Open Circuit open
Active open ON
Active closed OFF
Close Short-circuit
Active open OFF
Active closed ON
Output
The output has three contacts: normally open (NO), normally closed (NC) and common
The output can be configured so that the contacts change status when one or more events occur, with
different programming options (see Menu).
Compared to the common contact, the NO and NC contacts have the following electrical characteristics:
Characteristics
Maximum limit
(1)
Maximum switchable voltage 150 VDC / 250 VAC.
Breaking capacity
2 A @ 30 VDC, 0,8 A @ 50 VDC, 0,2 A @ 150 VDC,
4A @ 250 VAC
Dielectric strength between contact and internal coil 1000 V AC (1 minute @ 50 Hz).
(1)
data relating to a resistive load
Input parameters
The input can be configured in the Settings-Modules-Ekip Signalling 1K-Input menu:
Parameter Description Default
Polarity
Defines whether the input is interpreted as ON by the Trip unit when it is
open (Active open) or when it is closed (Active Closed)
Active closed
Delay
Minimum activation time of the input before status change is recognized;
the delay is given in seconds and can be set within range: 0 s to 100 s, in
0.01 s steps
NOTES:
status change is not recognized if the input deactivates before this
time has elapsed
if delay = 0 s status change must still be more than 300 µS
0.1 s

Table of Contents

Other manuals for ABB SACE Tmax XT5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Tmax XT5 and is the answer not in the manual?

ABB SACE Tmax XT5 Specifications

General IconGeneral
BrandABB
ModelSACE Tmax XT5
CategoryCircuit breakers
LanguageEnglish

Related product manuals