3. TRANSPORT AND HANDLING
The units are delivered from the factory ready for installation.
3.1 BY RECEIVING INSPECTION
Upon receiving the SafeRing / SafePlus please check that the
delivered equipment has not been damaged during transport.
If any such damage has occurred, a claim must be submitted
to the carrier immediately.
After unpacking, the following must be checked:
1. Operating handle – one piece should be included, normally
fixed on right-hand side.
2. Check that the pointer on the pressure indicator is in the
green area.
3. Carry out a function test on the mechanical parts.
4. Visual check of the switchgear.
Any faults or omissions must be reported immediately to
the supplier.
3.2 STORAGE
SafeRing / SafePlus must be stored under cover in a dry and
well ventilated area until it is installed and put into operation.
NOTE:
Use only approved slings when lifting.
Maximum angle on lifting lugs is set to 60
o
.
Weight table
Maximum weights for standard SafeRing
2-way DeV 300 kg 2-way DeF 300 kg
3-way CCV 450 kg 3-way CCF 450 kg
4-way CCCV 600 kg 4-way CCCF 600 kg
4-way CCVV 600 kg 4-way CCFF 600 kg
3-way CCC 450 kg
4-way CCCC 600 kg
SafePlus
Standard 1-way 150 kg
2-, 3- and 4-way as for SafeRing
5-way 750 kg
M - metering module incl. trafo 250 kg
Mt - metering tariff module incl. trafo 350 kg
The weights are without additional equipment, except for
transformers for M- and Mt-modules
SafeRing / SafePlus is fitted with lifting lugs, but can also be
moved on a pallet with a forklift truck. Make sure to secure
the switchgear.
Max angle 60
o