Manual ZX0 HB 600 en - Revision 05 | 35
The conditions for commissioning of the switchgear are as follows:
Supply voltage is available.
There are no active SF
6
gas pressure alarms.
Visual examination and sample checks on installation in
accordance with this document have been performed.
External control cables and wiring have been installed.
Testing of the specified protection data of the secondary
equipment has been successfully performed.
Protection testing has been passed.
Testing of all mechanical and electrical functions of the
switching devices and corresponding operating mecha-
nisms has been successfully performed.
Testing of the panel and switchgear interlocks has been
successfully performed.
Several trial switching operations (without service voltage)
on all switching devices have been successfully performed.
Switch positions are correctly displayed on the panels and
– if necessary – in the control room.
If remote control systems are fitted, these have been suc-
cessfully tested.
3 Commissioning
3.1 Conditions for
commissioning of the
switchgear
Unused voltage transformer sockets and extendable bus-
bar sockets have been closed off with insulating blanking
plugs.
Unused outer cones have been closed off and insulated.
High voltage testing at 80 % of rated short-duration power-
frequency withstand voltage U
d
to IEC 62271 - 200 has
been passed.
High voltage cables have been installed (after performance
of high voltage testing).
All cladding and covers have been fitted.
The following accessories have been handed over to the
operators:
This manual
The corresponding documents and order documents
Double bit key or barrel lock key for opening and closing
of the low voltage compartment doors
Levers and cranks for operation of the operating mecha-
nisms (see list of accessories)
Earthing set (optional)
Plug-in indicator unit for capacitive indication – if neces-
sary (see section 5.1)
Phase comparator in the case of more than one incom-
ing feeder (optional)
a work instruction for handling of SF
6
(an example can be
found in instruction manual HB 605/E) is displayed in the
switchgear room.
The operators have been instructed in the theory and prac-
tice of operation of the switchgear and are familiar with all
details of operation.