66 | Manual ZX0 HB 600 en - Revision 05
Comply with the safety regulations to EN 50110.
Isolate the switchgear section to be tested in accordance
with section 4.
est the switchgear section for the off-circuit condition as
described in section 5.1.
Earth the switchgear section and secure the working area
in accordance with section 4 and EN 50110 standard.
Switch the mcbs
1)
of the relevant operating mechanisms
off in order to prevent the switchgear section being ener-
gized by remote control.
Dismantle the cover on the relevant cable termination com-
partment.
?
Isolate all voltage transformers inside the switch-
gear section to be tested by operating the
isolating device (see section 4.5).
?
Remove plugged-in voltage transformers inside the
switchgear section to be tested as described in
section 2.3.5.2
?
In the course of testing, the test voltage is applied
in sequence to every conductor in the main circuit,
with the other conductor earthed. Do not exceed the maxi-
mum test voltage (80 % of the rated short-duration power
frequency withstand voltage (U
D
) as stated on the type plate).
Comply with the test conditions as set out in IEC 62271-200.
In the case of a sectionalizer (without circuit-
breaker), application of the test voltage to the
busbar in operation is not permissible. Earth the
system section concerned for the duration of the test (figure
5. 3. 2.1).
Close off free inner cone sockets (for plugged-in voltage
transformers) (Section 2.4.3).
Remove any surge arresters fitted in accordance with the
manufacturer’s instructions.
Close off free outer cones within the system section to be
tested with blanking plugs in accordance with the manu-
facturers instructions.
Short-circuit the secondary terminals of the block-type
current transformers installed in the test circuit (in section-
alizers, risers and metering panels) and earth them.
Short-circuit the sockets for the capacitive indicator
system in the relevant switchgear section using the short-
circuiting plug.
Fit the high voltage testing set to the (outer cone) cable
connector system of the panel to which the test voltage is
to be applied, following the manufacturer’s instructions.
Connect the test transformer to the test plug or test cable
and earth the other two phases of the test system.
Connect the second terminal of the test transformer to
system earth.
Connect other sections of the switchgear to be tested by
operating the relevant disconnectors and circuit-breakers.
Cancel the earthing of the system section to be tested
before applying the test voltage.
Perform the high voltage test.
Earth the system section on completion of individual tests
and on conclusion of testing.
Dismantle the test cables or test plugs.
Fit any surge arresters and voltage transformers required.
Close off any free test sockets and cable sockets with
blanking plugs.
Close off free outer cones with insulating blanking plugs in
accordance with the manufacturer’s instructions.
Cancel any isolation of voltage transformers.
Remove the short-circuiting plugs from the capacitive
indicator.
Refit the cover on the cable termination compartment.
Busbar to be tested
Earthed busbar
Fig. 5.3.2.1: Voltage test in case of a sectionalizer (without circuit-breaker)
5.3.2 Voltage test of the main circuit
1)
mcb: miniature circuit-breaker