EasyManuals Logo
Home>Allen-Bradley>Control Unit>1769-OF8C

Allen-Bradley 1769-OF8C User Manual

Allen-Bradley 1769-OF8C
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
8 Compact 1769-OF8C Analog Output Module
Publication 1769-IN065B-EN-P - September 2005
Module Spare/Replacement Parts
Terminal block, catalog number 1769-RTBN12 (1 per kit)
(A-B part number A22112-319-01)
Door, catalog number 1769-RD (2 per kit)
Field Wiring Connections
Grounding the Module
This product is intended to be mounted to a well-grounded mounting surface such
as a metal panel. Additional grounding connections from the module’s mounting
tabs or DIN rail (if used), are not required unless the mounting surface cannot be
grounded. Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional information.
System Wiring Guidelines
Consider the following when wiring your system:
All module commons (ANLG COM) are connected in the analog module.
The analog common (ANLG COM) is not connected to earth ground inside
the module.
Channels are not isolated from each other.
Use Belden 8761, or equivalent, shielded wire.
Under normal conditions, the drain wire and shield junction must be
connected to earth ground, via a panel or DIN rail mounting screw at the
analog I/O module end. Keep the shield connection to ground as short as
possible.
(1)
To ensure optimum accuracy, limit overall cable impedance by keeping your
cable as short as possible. Locate the I/O system as close to your sensors or
actuators as your application will permit.
Current outputs (Iout 0+ to Iout 7+) of the 1769-OF8C module source
current that returns to ANLG COM. Load resistance for a current output
channel must remain between 0 and 500 .
(1)
In environments where high frequency noise may be present, it may be necessary to ground the shield via a 0.1µF capacitor
at the load end and also ground the module end without a capacitor.