56 Rockwell Automation Publication 2080-UM004C-EN-E - March 2015
Appendix 5 DeviceNet Plug-in – 2080-DNET20
Send Explicit Messages to
2080-DNET20 Plug-in Using
Micro800 Pass Through
MSG_CIPGENERIC instruction can be used to send Explicit messages to the
2080-DNET20 plug-in and the Slave nodes on the DeviceNet network.
In MSG_CIPGENERIC, configure the target path as mentioned below:
To access the plug-in, the format of the target path is “1, Slot number”.
To access a Slave device through the plug-in, the format of the target path is
“1, Slot number, 2, DeviceNet node address.
For example, if the 2080-DNET20 plug-in is connected at physical slot 3 and the
Slave device of address 40 is present in the DeviceNet network, then:
Using MSG_CIPGENERIC to access the plug-in, the target path would
be “1, 3.
Using MSG_CIPGENERIC to access the Slave node through the plug-in,
the target path would be “1, 3, 2, 40”.
Note that the number “1” refers to the Virtual backplane port number and “2”
refers to the 2080-DNET20 plug-in's DeviceNet port number. These are fixed
values. The slot number starts from 1 up to the maximum number of slots
physically present in the controller.
When the controller pass through feature is used in the following example:
Micro850 –> Micro820 [192.168.1.100] –> 2080-DNET20 plug-in
[Slot 3] –> Slave device [Node 40]
Using MSG_CIPGENERIC starting from Micro850 to access the plug-
in, the target path would be “4, 192.168.1.100, 1, 3”
1 Transaction completed successfully.
2 Transaction in progress (not ready).
4 Error – node offline
5 Error – DeviceNet port disabled/offline
6 Error – Transaction TXID unknown
7 Error – Duplicate TXID
9 Error – Scanner out of buffers
12 Error – Response data too large for block
14 Error – Invalid size specified
15 Error – Device timed out
16 Block queued.
17 Block allocated
18 Connection in progress
3, 8, 10, 11, 13, 19...255 Reserved
Explicit Message Status Codes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 2080-MEMBAK-RTC and is the answer not in the manual?

Allen-Bradley 2080-MEMBAK-RTC Specifications

General IconGeneral
BrandAllen-Bradley
Model2080-MEMBAK-RTC
CategoryController
LanguageEnglish

Related product manuals