40 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 1 Installation/Wiring
General Notes
All Drive Frames
• The motor cable should be kept as short as possible in order to avoid
electromagnetic emission as well as capacitive currents.
• Use of line filters in ungrounded systems is not recommended.
• Conformity of the drive with CE EMC requirements does not
guarantee an entire machine installation complies with CE EMC
requirements. Many factors can influence total machine/installation
compliance.
Frame C Drives Only
• If the plastic top panel is removed or the optional conduit box is not
installed, the drive must be installed in an enclosure with side openings
less than 12.5 mm (0.5 in.) and top openings less than 1.0 mm (0.04 in.)
to maintain compliance with the LV Directive.
Essential Requirements for CE Compliance
Conditions 1...4 listed below must be satisfied for PowerFlex drives to meet
the requirements of EN61800-3.
1. Grounding as described in Figure 14
. Refer to page 20 for additional
grounding recommendations.
2. Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.
3. All shielded cables should terminate with the proper shield connector.
4. Conditions in Tab le 1 2
.
Table 12 - PowerFlex 400 – EN61800-3 Compliance
PowerFlex 400 Drive First Environment Restricted First Environment Unrestricted
kW
(HP)
Cat No.
22C-...
Required Filter
(Allen-Bradley)
Restrict
Motor
Cable to
(Meters)
Install
Drive and
Filter in
Shielded
Enclosure
Required Filter Restrict
Motor
Cable to
(Meters)
Install
Drive and
Filter in
Shielded
Enclosure
200...240 Volts
2.2 (3.0) B012N103 22-RF034-CS 10 No 22-RF034-CS 1 Required
3.7 (5.0) B017N103 22-RF034-CS 10 No 22-RF034-CS 1 Required
5.5 (7.5) B024N103 22-RF034-CS 10 No 22-RF034-CS 1 Required
7.5 (10) B033N103 22-RF034-CS 10 No 22-RF034-CS 1 Required
11 (15) B049A103 22-RFD070 150 Required Deltron MIF Series 50 Required
15 (20) B065A103 22-RFD100 150 Required Deltron MIF Series 50 Required
18.5 (25) B075A103 22-RFD100 150 Required Deltron MIF Series 50 Required
22 (30) B090A103 22-RFD150 150 Required Deltron MIF Series 50 Required