72 Rockwell Automation Publication 5069-UM003A-EN-P - May 2018
Chapter 5 Troubleshoot Your Module
Flashing green The following conditions exist:
Both channels are disabled.
The module is powering up.
The module has powered up successfully.
One of the following:
The module does not have a connection to the controller. A connection
can result from missing, incomplete, or incorrect
module configuration.
Complete the following:
Troubleshoot your Logix Designer application to determine what is
preventing a connection from the module to the controller and correct the
issue.
Confirm that the system conditions require the controller to be in Remote
Run mode or Run mode, transition the controller to one of those modes.
Steady red The module experienced a nonrecoverable fault. Complete the following actions:
1. Cycle power to the module.
2. If the status indicator remains in the steady red state, replace the module.
Flashing red One of the following conditions exist:
A module firmware update is in progress.
A module firmware update attempt failed.
The device has experienced a recoverable fault.
A connection to the module has timed out.
Complete one of the following:
Let the firmware update progress complete.
Reattempt a firmware update after one fails.
Use the Logix Designer application to determine the cause of the
module fault.
The Connection and Module Info categories of the modules configuration
indicate the fault type.
To clear a recoverable fault, complete one of the following:
Cycle module power.
Click Reset Module in the Logix Designer application project via the
Module Info category of the Module Properties dialog box.
If the fault does not clear after cycling power and clicking Reset Module,
contact Rockwell Automation® Technical Support.
Use the Logix Designer application to determine if a connection has timed
out. The Connection category in the Module Properties for the module
indicates the module state, including if a connection has timed out.
If a connection has timed out, determine the cause and correct it. For
example, a cable failure can cause a connection timeout.
Table 15 - Module Status Indicator - Compact 5000 I/O Module
Indicator State Description Recommended Action

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Compact 5000 and is the answer not in the manual?

Allen-Bradley Compact 5000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelCompact 5000
CategoryControl Unit
LanguageEnglish

Related product manuals