Produce and Consume a Tag
34 Rockwell Automation Publication 1756-PM011J-EN-P - February 2018
The RPI is outside the range of the producing controller’s RPI Limits. A
default RPI is set up for the producing controller. But, the network path
contains a bridge that blocks the negotiated RPI to prevent an interruption to
other controllers on the network.
Version 17 and earlier: The RPI requested by the consumed tag is not
within the range of the producer. The connection is rejected and a 0112 error
is reported that the connection failed. You must re-enter an RPI that is within
the range configured on the produced tag. If a version 17 consumer is trying
to connect with a version 18 producer and the RPI is outside the range of the
producer, a 0112 error reports the connection failed.
Tip:
See RPI I/O Faults on page 37
for an explanation of the error messages.
Version 18 and later: The RPI requested by the consumed tag is not within
the RPI limitation range of the producer. The producer is configured to
provide an RPI default. The producer sends the default RPI to the consumer,
but the consumer controller is not set up to accept a default RPI from the
producer. The negotiated RPI is disabled to prevent an interruption to the
multicast connection. A 0112 error message is reported and you must re-
enter an RPI within the range of the producer’s limits.