PanelView Component HMI Terminals 25
Publication 2711C-IN001H-EN-P - July 2014
4. Apply 24V DC power to the terminal.
Ground the Terminal
PanelView Component devices have a functional earth terminal that you must connect to a low-impedance
earth ground. The functional earth connection is on the power input terminal block. The negative power
terminal is not internally connected to earth ground.
The functional earth terminal wiring requires a minimum wire gauge.
Connect Devices
Use these cables for connecting devices to PanelView Component terminals.
ATTENTION: The functional earth connection to ground is mandatory. This connection is
required for noise immunity, reliability, and Electromagnetic Compliance (EMC) with the
European Union (EU) EMC directive for CE-mark conformance.
Functional Earth Wire Specifications
FE Symbol Wire Type Wire Gauge Terminal Screw Torque
Stranded or solid Cu 90 °C (194 °F) 2.08…3.31 mm
2
(14…12 AWG)
0.45…0.56 Nm (4…5 lb-in)
Cables for PanelView Component Terminals
Cat. No. Description For Use With
2711C-CBL-UU02 USB-A host to USB-B device cable, 2 m (6.56 ft) C200, C300, C400, C600, C1000
2711P-CBL-EX04 Ethernet crossover CAT5 cable 4.3 m (14 ft) C400, C600, C1000
2711C-RCSD USB to SD adapter with secure digital (SD) card C200, C300, C400, C600, C1000
DC
+
Functional
Earth Ground
to Ground Bus
DC
-
44887