1-10 Installation/Wiring
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Shielded
Reflected Wave Protection
The drive should be installed as close to the motor as possible.
Installations with long motor cables may require the addition of external
devices to limit voltage reflections at the motor (reflected wave
phenomena). See Table 1.E
for recommendations.
The reflected wave data applies to all frequencies 2 to 10 kHz.
For 240V ratings, reflected wave effects do not need to be considered.
Table 1.E Maximum Cable Length Recommendations
Output Disconnect
The drive is intended to be commanded by control input signals that will
start and stop the motor. A device that routinely disconnects then
reapplies output power to the motor for the purpose of starting and
stopping the motor should not be used. If it is necessary to disconnect
power to the motor with the drive outputting power, an auxiliary contact
should be used to simultaneously disable drive control run commands.
Location Rating/Type Description
Standard
(Option 1)
600V, 75°C or 90°C (167°F
or 194°F) RHH/RHW-2
Belden 29501-29507 or
equivalent
Four tinned copper conductors with XLPE insulation
Foil shield and tinned copper drain wire with 85% braid
coverage
PVC jacket
Standard
(Option 2)
Tray rated 600V, 75°C or
90°C (167°F or 194°F)
RHH/RHW-2
Shawflex 2ACD/3ACD or
equivalent
Three tinned copper conductors with XLPE insulation
5 mil single helical copper tape (25% overlap min.)
with three bare copper grounds in contact with shield
PVC jacket
Class I & II;
Division I & II
Tray rated 600V, 75°C or
90°C (167°F or 194°F)
RHH/RHW-2
Three tinned copper conductors with XLPE insulation
5 mil single helical copper tape (25% overlap min.)
with three bare copper grounds in contact with shield
PVC copper grounds on #10 AWG and smaller
Reflected Wave
380-480V Ratings Motor Insulation Rating Motor Cable Only
(1)
(1)
Longer cable lengths can be achieved by installing devices on the output of the drive.
Consult factory for recommendations.
1000 Vp-p 15 meters (49 feet)
1200 Vp-p 40 meters (131 feet)
1600 Vp-p 170 meters (558 feet)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 4M and is the answer not in the manual?

Allen-Bradley PowerFlex 4M Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 4M
CategoryController
LanguageEnglish

Related product manuals