Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 55
The RPI is selectable, since it is a direct connection.
6. Verify that the requested packet interval (RPI) is appropriate for your
system (10 ms for this example). You use this value for the
rack-optimized connection to the I/O modules.
7. Click OK to accept the configuration.
The 1734-AENT adapter appears indented under the local 1734-ENBT in
the I/O Configuration folder.
Add the POINT I/O Module and Configure For Rack Optimization
1. Right-click the 1734-AENT adapter under the I/O Configuration
folder, and select New Module.
IMPORTANT
To avoid overloading the 1734-AENT adapter, we
recommend that the RPI be no less than 10 ms for rack
connections and 50 ms for direct connections.
IMPORTANT
If you exceed the 1734-AENT chassis size, trying to add
more modules than you configured, the New Module
selection appears dim and is disabled. Increase the
1734-AENT chassis size to add more POINT I/O
modules.

Table of Contents

Other manuals for Allen-Bradley Rockwell Automation 1734-AENT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Rockwell Automation 1734-AENT and is the answer not in the manual?

Allen-Bradley Rockwell Automation 1734-AENT Specifications

General IconGeneral
Model1734-AENT
CategoryNetwork Hardware
TypeEtherNet/IP Adapter
Ethernet Ports2
IP AddressingStatic or DHCP
Network AddressConfigurable via software
MountingDIN rail
Number of Ports2
Port TypeRJ45
Communication ProtocolEtherNet/IP
ManufacturerRockwell Automation
Power Supply24V DC
EnclosureOpen-style

Related product manuals