Product Description
Autopulse-442R 50098:F 05/24/2001 11
2SWLRQDO0HWHUV
9ROWDJHDQG&XUUHQW0HWHUV;00
The Meter Module provides a voltmeter to measure the
voltage across the batteries and an ammeter to measure the
charging current to the batteries. The meters are provided as
an assembly that mounts to the lower left-hand corner of the
cabinet.
6SHFLILFDWLRQV
$&3RZHU
Autopulse-442R and Autopulse-442RC: 120 VAC, 50/60 Hz, 1.2 amps
Autopulse-442RE: 220/240 VAC, 50/60 Hz, 0.6 amps
Wire size: minimum #14 AWG with 600 V insulation
%DWWHU\OHDGDFLGRQO\
Maximum Charging Circuit: 27.6 VDC, 1.5 amps
Maximum Battery Capacity: 18 AH. (Batteries larger than 12 AH require
Notifier BB-17 or other UL-listed external battery cabinet.)
Minimum Battery Capacity: 7 AH
,QLWLDWLQJ'HYLFH&LUFXLWV
Power-limited circuitry
Operation: Style D (Class A)/Style B (Class B)
Normal Operating Voltage: 24 VDC (ripple = 1.0 V p-p)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: 100 ohms
End-of-Line Resistor: 4.7K, 1/2-Watt (part # 418334, UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including End-of-Line Resistor)
1RWLILFDWLRQ$SSOLDQFHDQG5HOHDVLQJ&LUFXLWV
Power-limited circuitry
Maximum allowable voltage drop due to wiring: 2 VDC
Normal Operating Voltage: 24 VDC
Total current available to all external devices: 2.25 amps
Maximum signaling current per circuit: 1.5 amps
End-of-Line Resistor: 4.7K, 1/2-Watt (part # 418334, UL listed)
$ODUPDQG7URXEOH5HOD\V
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). Any
power connected to these relay contacts must come from a power-limited supply. Fail-safe
operation ensures trouble relay functions under loss of both primary power (AC) and secondary
(battery).
0
10
20
30
DC VOLTS
0
5
5
DC AMPERES
[PPFGU
[$&&W%NWLI
AC Circuit Breaker

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul AUTOPULSE 442R and is the answer not in the manual?

Ansul AUTOPULSE 442R Specifications

General IconGeneral
BrandAnsul
ModelAUTOPULSE 442R
CategoryControl Systems
LanguageEnglish

Related product manuals