6 Autopulse-442R 50098:F 05/24/2001
Section 1 Product Description
The Autopulse-442R/442RE Fire Alarm Control Panel has been designed as a control center for
use in automatic fire suppression systems. The Autopulse-442R/442RE is a feature-packed
control unit suitable to perform detection and control functions associated with the release of
gaseous agent/special hazard fire protection systems. The panel is designed for maximum
reliability with 100% solid state circuitry and isolated relay contacts for outside interfacing. The
panel features programmable options to allow on-site customization of the unit for various
operating configurations.
The Autopulse-442R/442RE is supplied complete with backbox, hinged door, control switches,
and indicator LEDs. The Autopulse-442R is a 120 VAC fire alarm control panel. The
Autopulse-442RE is an export version of the Autopulse-442R that runs on 220/240 VAC. The
Autopulse-442RC is a 120 VAC control unit that functions according to the requirements of
Underwriters Laboratories of Canada (ULC). An integral standby battery system, with charger,
is provided. In case of commercial AC power interruption, automatic switchover to the battery
system will provide power to the panel for a minimum of 24 hours.
)HDWXUHV
* Applications which require the 411UDAC, the NOTI-FIRE 911AC, or the Potter EFT-C are not
FM approved.
&LUFXLWV
,QSXW&LUFXLWV
Detector Zone 1, Style D (Class A)/Style B (Class B)
Detector Zone 2, Style D (Class A)/Style B (Class B)
Abort, Style D (Class A)/Style B (Class B)
Manual Release, Style D (Class A)/Style B (Class B)
Microprocessor-controlled
Power-limited on all circuits except
Municipal Box output and Releasing
Circuits
Alarm and trouble resound
Four Style D (Class A) / Style Y (Class B)
Initiating Device Circuits
Two Style Z (Class A) / Style Y (Class B)
Notification Appliance Circuits
Two Style Y (Class B) Releasing Circuits
General alarm and trouble relays
Optional module for 4 zone/function
relays (4XZM)
Optional transmitter module (4XTM).
Optional volt/amp meter module (4XMM)
Optional supervised remote annunciator
(RZA-4X) Requires LED Interface
Module (4XLM)
Optional digital communicator
(411UDAC)
Supervisory Input Option
Delay timer (adjustable)
Three abort function options
Designed for suppression standards
Disable/enable controls per initiating zone
Last Event Recall
Battery/Earth fault supervision
Fuse protection on all Notification/Release
Circuits
RMS regulated output power, 2.25 amps
7 amp-hour (AH) to 18 AH battery
options, up to 90 hours standby
Resettable and nonresettable regulated
power outputs
Extensive transient protection
Watchdog timer to supervise
microprocessor
Output circuits protected against false
activations
Slide-in zone identification labels
Steel cabinet 14.5 in (368.3 mm) wide by
16 in (406.4 mm) high by 5 in (127 mm)
deep
Dead-front dress panel option (DP-4X)
(Required for Canadian applications)
Trim ring for flush mount between 16 in
(406.4 mm) center studs (TR-4XR)
Abort and manual release circuits
Cross-zone option