Installation Procedure
Autopulse-442R 50098:F 05/24/2001 15
,QLWLDWLQJ'HYLFH&LUFXLWV
=RQHV
Wire all alarm initiating devices sequentially for proper supervision. Initiating devices include
manual pull stations, waterflow alarm devices, and heat-, photoelectric-, and ionization-type
detectors. Refer to the Device Compatibility Document for compatible devices.
Notes:
1. Observe polarity when connecting polarized devices.
2. All circuits are supervised and power-limited.
3. Leave dummy load resistor (provided) on all unused circuits.
% $ $ % % $ $ % % $ $ % % $ $ %
%

53,'&FGU
,1  ,1
,1
,1 
Manual
Pull Station
Heat
Detector
Two-wire
Smoke
Detector
Style B (Class B)
Initiating Device Circuit
4.7K, 1/2-Watt (part # 418334, UL listed)
Style D (Class A)
Initiating Device Circuit
Abort Switch
4.7K, 1/2-Watt
(part # 418334,
UL listed)
Manual Release
4.7K, 1/2-Watt
(part # 418334,
UL listed)
Figure 2.2 Initiating Device Circuits