Product Description
10 Autopulse-442R 50098:F 05/24/2001
/(',QWHUIDFH0RGXOH;/0
The LED Interface Module supports the RZA-4X Remote Annunciator
module. Annunciator wiring is supervised for open conditions by this
module. The Annunciator Driver Module mounts to the main board on
the J8 option connectors.
Specifications
Maximum voltage/current, each output: 27.6 V / 8 mA.
Outputs are power-limited.
=RQH5HOD\0RGXOH;=0
The Zone Relay module provides Form-C contacts for the following:
Alarm detected (either zone/mode)
First alarm, second alarm (Cross zone mode)
Release
General Alarm
System Trouble
Specifications
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps
@ 30 VAC (resistive)
5HPRWH$QQXQFLDWRU
5HPRWH$QQXQFLDWRU5=$;
The Remote Annunciator mounts on a standard single-gang
box, and provides LED indication of the same functions as
the zone relay module. For example with DIP 1=ON and
DIP 2=OFF:
One zone in Alarm (red)
Two zones in Alarm (red)
Releasing Circuit 1 (red)
Releasing Circuit 2 (red)
System Trouble (yellow)
A Local Trouble Sounder and Silence Switch are also
provided. All LED wiring is supervised for open conditions.
Any open condition will cause the System Trouble LED to
illuminate.
Note: The Remote Annunciator requires the use of an LED
Interface module (4XLM).
[OPWLI[]PZPI
5]D[IUZPI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul AUTOPULSE 442R and is the answer not in the manual?

Ansul AUTOPULSE 442R Specifications

General IconGeneral
BrandAnsul
ModelAUTOPULSE 442R
CategoryControl Systems
LanguageEnglish

Related product manuals