EasyManuals Logo
Home>Ansul>Control Systems>AUTOPULSE 442R

Ansul AUTOPULSE 442R User Manual

Ansul AUTOPULSE 442R
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
Product Description
Autopulse-442R 50098:F 05/24/2001 9
2YHUYLHZRI',36ZLWFK6:)XQFWLRQV
2SWLRQDO%RDUGV
The control panel has mounting slots for two optional boards. Any two
of the three optional modules may be installed.
7UDQVPLWWHU0RGXOH;70
The Transmitter Module provides a supervised output for local energy
municipal box transmitter (for NFPA 72 Auxiliary Fire Alarm System)
and alarm and trouble reverse polarity circuits (for NFPA 72 Remote
Station Fire Alarm System). Also included is a DISABLE switch and
disable trouble LED.
As a jumper option, the alarm reverse polarity circuit will open on
trouble if no alarm exists.
Specifications for Local Energy Municipal Box service (NFPA 72
Auxiliary Fire Alarm System)
Supervisory current: 5.0 mA
Trip current: 0.35 amps. (Subtracted from Notification Appliance power)
Coil Voltage: 3.65 VDC
Coil resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building.
Specifications for Remote Station service (NFPA 72 Remote Station Fire Alarm System)
Maximum load for each circuit: 10 mA.
Reverse polarity output voltage: 24 VDC.
Remote Alarm and Remote Trouble wiring can leave the building.
DIP 1 Cross-zone OFF NAC 1 and 2, with Zone 1 or 2
NAC 2 runs at 60ppm then steady on time-out (unless frozen by abort)
Releasing Circuit 3 activated at time-out
Releasing Circuit 4 activated at time-out if not set as supervisory
ON NAC 1 on with first alarm, off on second alarm zone
NAC 2 on with both Zone 1 and 2. 60ppm and steady after time-out. Frozen by abort.
Releasing Circuit 3 activated at time-out
Releasing Circuit 4 activated at time-out if not set as supervisory
DIP 2 Supervisory OFF NAC Circuit 4 = Releasing Circuit
ON NAC Circuit 4 = Supervisory Circuit
DIP 3,
DIP 4
Timer OFF, OFF = No delay
OFF, ON = 10 second delay
ON, OFF = 20 second delay
ON, ON = 30 second delay
Note: Timer starts on Zone 1 or 2 alarm, or both Zone 1 and Zone 2 if set for cross-zone.
DIP 5,
DIP 6
Abort OFF, OFF = Standard UL abort (Deadman abort)
OFF, ON = IRI delay timer abort
ON, OFF = NYC delay timer abort
ON, ON = Local AHJ delay timer abort
Note: See Setting Mode of Operation in Section 2.10 for a more detailed explanation of DIP switch functions.
[WPLVFGU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul AUTOPULSE 442R and is the answer not in the manual?

Ansul AUTOPULSE 442R Specifications

General IconGeneral
BrandAnsul
ModelAUTOPULSE 442R
CategoryControl Systems
LanguageEnglish

Related product manuals