Model 8800 Communicating Thermostat
Model 8800 Communicating Thermostat
Programmers Manual
READ AND SAVE THESE INSTRUCTIONS
TABLE OF CONTENTS
Introduction............................................. 1
Protocol ................................................ 1
System Interface ........................................ 2
Timing and Synchronization .............................. 2
Host Message Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Response Expected ...................................... 3
No Response Expected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Node Message Types .................................... 3
Explicit Address Command Response ....................... 4
Global Address Command Response ........................ 4
Unsolicited Message.....................................4
Command Syntax . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Host Command Syntax ................................... 5
Node Message Syntax ................................... 5
Commands Table of Contents ............................. 6
Command Details........................................ 8
Thermostat Configuration Commands ....................... 8
Communication Control Commands . . . . . . . . . . . . . . . . . . . . . . . . 15
Change of State Report Control Commands ................. 18
Setup Commands ...................................... 20
Alarm Commands ...................................... 25
Lockout Commands ..................................... 27
Sensor Commands......................................31
Temperature Control Commands .......................... 36
Humidity Control Commands ............................. 44
Program and Schedule Commands......................... 46
Status Commands ...................................... 52
Messaging Commands .................................. 55
INTRODUCTION
This document contains information needed to write interface code for the Aprilaire Model 8800 Communicating Thermostat. For wiring and
thermostat setup refer to the 8800 System Installation Manual (RPC part no. 10009416).
PROTOCOL
The proprietary ASCII protocol is for communication between a Host controller and up to 64 Model 8800 Communicating Thermostats. The
protocol is based upon the Model 8870 Communicating Thermostat protocol, but has an expanded command set to utilize the additional features
of the Model 8800 Communicating Thermostat.
1

Other manuals for Aprilaire 8800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aprilaire 8800 and is the answer not in the manual?

Aprilaire 8800 Specifications

Thermal Specifications IconThermal Specifications
control temperature range45º to 99ºF (7º to 32ºC)
display temperature range32º to 99ºF (0º to 40ºC)
accuracy± 1ºF (± .5ºC)
Operating Environment IconOperating Environment
storage temperature-30º to 140ºF (-34.4º to 60ºC)
operating humidity5% to 90% relative humidity
operating ambient temperature32º to 120ºF (0º to 48.9ºC)
Electrical Specifications IconElectrical Specifications
voltage AC24 VAC (18-30 VAC)
maximum load per terminal1 amp
total maximum load2.5 amp
Screen IconScreen
screen size10.3 sq. in.
backlitconstant low intensity light option
font sizelarge
Weight and Dimensions IconWeight and Dimensions
height4 15/16 inches
width6 inches
depth1 5/16 inches