Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
25 mm² < 110 A < 96 A < 87 A < 78 A < 67 A
35 mm² < 137 A < 119 A < 108 A < 97 A < 84 A
50 mm² < 167 A < 145 A < 132 A < 119 A < 102 A
Calculation method for IEC:
Single supply cables (3 phases + PE - configuration (1)):
Add 10 % to the total compressor current (I
tot
Pack or I
tot
FF from the tables)
Install the prescribed fuse on each cable
Parallel supply cable (2 x 3 phases + PE - configuration (2)):
Add 10 % to the total compressor current (I
tot
Pack or I
tot
FF from the tables) and divide by 2
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Install fuses of half the size of the recommended maximum fuse size on each cable.
When using 2 x 3 phases + PE as in (3):
Add 10 % to the total compressor current (I
tot
Pack or I
tot
FF from the tables) and divide by √3
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Fuse size: the recommended maximum fuse size divided by √3 on each cable.
Size of the PE cable:
For supply cables up to 35 mm²: same size as supply cables
For supply cables larger than 35 mm²: half the size of the supply wires
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is recommended).
Example: I
tot
= 89 A, maximum ambient temperature is 45 °C, recommended fuse = 100 A
Single supply cables (3 phases + PE - configuration (1)):
I = 89 A + 10 % = 89 x 1.1 = 97.9 A
The table for B2 and ambient temperature = 45 ° C allows a maximum current of 93 A for a 50 mm²
cable. For a cable of 70 mm², the maximum allowed current is 118 A, which is sufficient. Therefore,
use a 3 x 70 mm² + 35 mm² cable.
If method C is used, 50 mm² is suffficient. (35 mm² for method F) => cable 3 x 50 mm² + 25 mm².
Parallel supply cable (2 x 3 phases + PE - configuration (2)):
I = (89 A + 10 %)/2 = (89 x 1.1)/2 = 49 A
For a cable of 25 mm², B2 at 45 °C, the maximum current is 63 A x 0.8 = 50.4 A. So 2 parallel cables
of 3 x 25 mm² + 25 mm² are sufficient.
Install 50 A fuses on each cable instead of 100 A.
Fuse calculations for IEC are done according to 60364-4-43 electrical installations of buildings, part 4:
protection for safety- section 43: protection against overcurrent. Fuse sizes are calculated in order to protect
the cable against short circuit. Fuse type aM is recommended but gG/gL is also allowed.
9.3 Reference conditions and limitations
Reference conditions
Air inlet pressure (absolute) bar 1
Air inlet pressure (absolute) psi 14.5
Air inlet temperature ˚C 20
Instruction book
2920 7104 10 91

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Atlas Copco GA 22 MED and is the answer not in the manual?

Atlas Copco GA 22 MED Specifications

General IconGeneral
BrandAtlas Copco
ModelGA 22 MED
CategoryAir Compressor
LanguageEnglish

Related product manuals