103
Instruction book
9096 3321 00
14. Additives
If it should be necessary to use additives in the cooling water, take into account that the cooling capacity will
change.
Remarks:
• Chloride and sulphate are interactive. In pass-through systems the sum of the squares must not
exceed 85000. For recirculating systems with proper controls and treatment, the sum of the squares may be
up to 520000. Note that the sulphate value must include any sulphite present.
• Cooling capacity will change If additives are used
6.5 Pictographs
Description
Reference Designation
1 Automatic condensate drain
2 Warning: voltage
3 Warning: switch off the voltage and depressurise compressor before repairing
4
Warning: before connecting compressor electrically, consult Instruction book for
motor rotation direction