EasyManuals Logo
Home>Beckhoff>Industrial Equipment>BK5250

Beckhoff BK5250 User Manual

Beckhoff BK5250
47 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
Product overview
BK52x0 and LC5200 11Version: 2.0.0
2.4 Technical data
Technical data BK5200 BK5210 BK5250 LC5200
Number of Bus Terminals 64 64 (255 with K-
bus extension)
64
Digital peripheral signals 512 inputs/outputs 256 inputs/
outputs
1,020 inputs/
outputs
256 inputs/
outputs
Analog peripheral signals 256 inputs/outputs - 256 inputs/
outputs
-
Protocols
Configuration possibility via the KS2000 configuration software or the controller (TwinCAT)
Maximum number of bytes 512bytes of input
data, 512bytes of
output data
32bytes of input
data, 32bytes of
output data
512bytes of input
data, 512bytes
of output data
32bytes of input
data, 32bytes of
output data
Bus connection 1 x open pluggable connector, 5-pin directly to spring-
loaded terminal
Power supply 24V
DC
(-15%/+20%), via bus cable 11 … 25V
(according to DeviceNet specification)
Input current 70mA+(total K-bus current)/4, 500mA max.
Input inrush current approx. 2.5xcontinuous current
K-bus power supply up to 1750mA 500mA 1750mA 500mA
Power contact voltage maximum 24V
DC
Power contact current load maximum 10A
Dielectric strength 500V (power contact / supply voltage / Bus Coupler)
Recommended fuse ≤ 10A
Mounting [}20]
on 35mm support rail according to EN60715
Weight app.150g approx.130g approx.100g approx.100g
Permissible ambient
temperature range during
operation
0°C ... +55°C 0°C ... +55°C -25°C ... +60°C
(ET)
0°C ... +55°C
Permissible ambient
temperature range during
storage
-25°C... +85°C -25°C... +85°C -40°C... +85°C -25°C... +85°C
Permissible relative humidity 95%, no condensation
Vibration/ shock resistance conforms to EN60068-2-6/ EN60068-2-27
EMC immunity/emission conforms to EN61000-6-2/ EN61000-6-4
Installation position variable
Protection class IP20
Approvals/markings CE, cULus,
ATEX [}28]
CE, cULus, GL,
ATEX [}28]
CE, cULus,
ATEX [}29]
CE, cULus,
ATEX [}28]
System data DeviceNet BK5200, BK5210, BK5250, LC5200
Number of I/O modules 64
Data transfer medium shielded, twisted copper wire with energy supply, 5-pin
Max. cable length 500m 250m 100m
Data transfer rates 125kbaud 250kbaud 500kbaud
Operation modes Bit-Strobe, Polling, Cyclic, Change-of-State (COS)
DeviceNet type Communications adapter
Ex marking
Standard Marking
ATEX II 3 G Ex nA IIC T4 Gc

Table of Contents