32
b
At the end of the siphon maintenance operations, it is recommended
to bring the boiler to condensing mode for a few minutes and to
check for leaks from the entire condensate evacuation line.
b
If the appliance is not used for more than 60 days, it is
necessary to ll the siphon in the boiler. If the boiler is
installed where the ambient temperature can remain above
30°C for prolonged periods, ll the siphon after a period of
30 days of inactivity. The operation must be carried out by
professionally qualied personnel.
5.1 Programmable parameters
A list of the programmable parameters is given below: USER (level al-
ways available) and INSTALLER (access with password 18); for a de-
tailed explanation of the parameters, refer to paragraph “5.2 Parameters
description”.
INSTALLER PARAMETERS
Value
min max
Password
level
Value set in
the factory
Personalised
values
CONFIGURATION
301
HYDRAULIC CONFIG. 0 4 INSTALLER 2 *
306
MIN FAN SPEED 1.200 3.600 INSTALLER see technical data table
307
MAX FAN SPEED 3.700 9.999 INSTALLER see technical data table
308
SLOW IGNITION ADJUSTMENT MIN MAX INSTALLER see technical data table
309
MAX CH FAN SPEED MIN MAX INSTALLER see technical data table
310
RANGE RATED MIN MAX_CH INSTALLER see technical data table
311
AUX OUTPUT 0 2 INSTALLER 0
312
FLUE GAS COUNTER RESET 0 1 INSTALLER 0
313
IGNITION SPEED IN RESTART AFTER
SHUTDOWN DUE TO TEMPERATURE
MIN FAN SPEED
SLOW IGNITION
ADJUSTMENT
INSTALLER
3.600 rpm
HEATING
405
SET PUMP NOT APPLICABLE ON THIS MODEL
408
OT+ CASCADE NOT APPLICABLE ON THIS MODEL
409
SCREED HEATER 0 1
INSTALLER
if boiler in OFF and LT
systems
0
410
HEATING OFF 0 min 20 min INSTALLER 3 min
411
RESET HEATING TIMES 0 1 INSTALLER 0
415
MAIN LT ZONE 0 1 INSTALLER 0
416 MAX TEMP (MAIN ZONE) MIN TEMP (MAIN ZONE) HT: 80.5 - LT: 45.0 INSTALLER HT: 80.5 - LT: 45.0
417 MIN TEMP (MAIN ZONE) 20
MAX TEMP (MAIN ZONE)
INSTALLER HT: 40 - LT: 20
418 THERMOREGULATION (MAIN ZONE) 0 1
INSTALLER
if ext. probe present
0
419 CURVE SLOPE (MAIN ZONE) HT: 1.0 - LT: 0.2 HT: 3.0 - LT: 0.8
INSTALLER
only if 418 = 1
HT 2.0 - LT 0.4
420 NIGHT-TIME COMP. (MAIN ZONE) 0 1 0
432 BUILDING TYPE 5 min 20 min 5 min
433 EXTERNAL PROBE REACTIVITY 0 255 20
DHW
508 MIN DHW TEMP. 37,5 °C 49,0 °C INSTALLER 37,5°C
509 MAX DHW TEMP. 49,0 °C 60,0 °C INSTALLER 60,0°C
511 SPEC. DHW FUNCTIONS 0 5 INSTALLER 0
HT. high temperature - LT: low temperature
USER PARAMETERS
Value
min max
Password
level
Value set in
the factory
Personalised
values
SETTINGS
004 MEASUREMENT UNIT 0 1 USER 0
006 BUZZER 0 1 USER 1
SERVICE PARAMETERS
Value
min max
Password
level
Value set in
the factory
Personalised
values
CONFIGURATION
302
PRESSURE TRANSD. TYPE 0 1 SERVICE 1
303
ENABLE FILLING 0 1 SERVICE 0
304
P
RESSURE AT START OF FILLING
NOT AVAILABLE ON THIS MODEL
305
VENTING CYCLE 0 1 SERVICE 1
HEATING
401
HIGH TEMP HYSTERESIS OFF
2 10 SERVICE 5
402
HIGH TEMP HYSTERESIS ON
2 10 SERVICE 5
403
LOW TEMP HYSTERESIS OFF
2 10 SERVICE 3
404
LOW TEMP HYSTERESIS ON
2 10 SERVICE 3
b
Some information might not be available depending on the access
level, machine status or system conguration.
C
A
B