EasyManuals Logo
Home>Bernard Controls>Controller>AQ Logic Series

Bernard Controls AQ Logic Series User Manual

Bernard Controls AQ Logic Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
English
21
4.6 Analog Input / Output (OPTION)
4.6.1 Analog signal types
Some actuator configurations can perform control functions in
response to a control signal.
4.6.2 Positioner configuration
To use this function, Positioner mode has to be activated:
using Logic menu - see §5.9.1
using Auxiliary Commands set with Proportional/ON-OFF - see
§5.8.1
The input signal is automatically calibrated on the stroke of the
actuator (0 - 100%), so there is no need to adjust the operating range
of the actuator.
The input signal is isolated from the ON/OFF commands and from the
remote position signal.
The actuator can still be operated in ON/OFF mode with the Open,
Close and Stop commands or using Proportional control. One of the
auxiliary commands must be used to select between these 2 control
modes.
In the standard configuration, Auxiliary Command is set on
Proportional/ON-OFF to allow the control mode to be selected
remotely:
Proportional = Analog control
ON/OFF = ON/OFF control.
For Analog Input/Output settings (e.g. Deadband), see §5.8.
Possible signals
Input impedance
(ohms)
Positioner board switch
setting (see §3.3.5):
for signals in mA, the
switch must be on mA
for signals in V, the
switch must be on V
4-20 mA
0-20 mA
4-12 mA
160
12-20 mA
160
0-10V
11000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bernard Controls AQ Logic Series and is the answer not in the manual?

Bernard Controls AQ Logic Series Specifications

General IconGeneral
BrandBernard Controls
ModelAQ Logic Series
CategoryController
LanguageEnglish

Related product manuals