Unit Configuration | 7Heat Pump Controller
8733819577 (2019/02)Heat Pump Controller Subject to change without prior notice
UNIT CONFIGURATION
Settings
The Bosch EasyStart app is used to configure available features of the HPC as follows:
Table 2 HPC Settings
Alarm Mode
The HPC has a fault alarm that can be configured
(via the Bosch EasyStart app) as constant or
pulsed. Constant configuration will energize and
latch the alarm output. The pulse alarm setting will
allow the alarm relay to pulse the alarm in sync
with the status LED indicator.
HPC Settings Default Settings
Freeze Protection Strategy 15°F–26°F 26°F
Cooling CFM per TON 300–450 400 CFM/Ton
Heating CFM per TON 300–450 375 CFM/Ton
Fan Only CFM reduction 50–100% 80%
Dehumidification CFM reduction 15–40% 15%
Heat Recover Package Enabled or Disabled Disabled
Heat Recovery Setpoint 110°F–140°F 120°F
Heat Recovery Sample Rate 2–6 Samples/Hr 3 Samples/Hr
Electric Heat Size None, 5kW, 10kW, 15kW, 20kW None
Low Loop Water Protection Enabled or Disabled Disabled
Low Loop Control Setpoint 20°F–50°F 34°F
Loop Pump Compressor Delay 30–240 seconds 30s
Mode of Compressor Operation Comfort or Economy Comfort
Down-Staging Latched or Unlatched Unlatched
Number of Lockouts 2–4 Strikes 3 Strikes
Lockout Reset (Y1) signal or (R) (Y1)
Units of Temperature °F or °C °F
Alarm Type Constant or Pulse Pulse
Date MM/DD/YYYY
Time HH:MM
High Efficiency Mode Enable or Disabled Disabled
Compressor Runtime Reset Write Only
Model Number
(from the Unit Data Plate)
SM036-1VTC-FRTADC-
CMGXXXXXD7HXXX4XXXXSNA
Serial Number
(from the Unit Data Plate) 1234-567-891011-1213141516
Refer to the “Updating the Firmware and
Configuring Unit Settings” section on page #26
for details on accessing these settings.
NOTICE: Keep the HRP configuration setting
set to disabled if there is no domestic water
supply available.