NOTE: With the battery installed and utility power available
to the transfer switch, the battery receives a trickle charge
whenever the engine is not running. It may take up to
72 hours to fully charge a battery with the trickle charge.
The trickle charge is not able to recharge a battery that is
completely discharged.
5. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery
terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
CAUTION
Installing the 15A fuse could cause the engine
to start.
DO NOT install this fuse until all plumbing and wiring has
been completed and inspected.
8. Set generator’s system switch to AUTO.
Servicing the Battery
If it is necessary to service the battery, proceed as follows:
1. Remove “Control Panel” access cover.
2. Set generator’s system switch to OFF.
3. Remove 15 Amp fuse from control panel.
4. Service or replace battery as required.
5. Connect red battery cable to battery positive terminal
(indicated by POSITIVE, POS, or (+)).
6. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-).
7. Ensure hardware on both positive and negative battery
terminals is secure.
8. Reinstall 15 Amp fuse in control panel.
9. Set generator’s system switch to AUTO.
10. Install “Control Panel” access cover.
11. Reset exercise timer. See Setting Exercise Timer.
To Clean the Generator
NOTICE
Improper treatment of generator can damage it and
shorten its life.
DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
DO NOT insert any objects through cooling slots.
Use a damp cloth to wipe exterior surfaces clean.
Use a soft, bristle brush to loosen caked on dirt, oil,
etc.
Use a vacuum cleaner to pick up loose dirt and debris.
Use low pressure air (not to exceed 25 psi) to blow
away dirt. Inspect cooling air slots and openings on
the generator. These openings must be kept clean and
unobstructed.
When Calling the Factory
You must have the following information at hand if it is
necessary to contact a local service center regarding service
or repair of this unit:
1. Obtain the unit Model Number and Serial Number from
the unit data decal. See Controls.
2. Obtain the engine Model/Type/Code numbers from the
engine label. See Controls. Please note that the model
number may vary slightly from that presented herein.
Storage
The Briggs & Stratton home generator is designed for
continuous backup operational duty. As such, there is
no need to take any storage precautions. However, if it
becomes necessary to take the system out of service for an
extended period, call Briggs and Stratton Technical Services
at (800) 743-4115, between 8:00 AM and 5:00 PM CT for
specific recommendations.

Other manuals for Briggs & Stratton 10000 Watt

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Briggs & Stratton 10000 Watt and is the answer not in the manual?

Briggs & Stratton 10000 Watt Specifications

General IconGeneral
Rated Maximum Load Current at 120 Volts83.33 Amps
Rated Maximum Load Current at 240 Volts41.66 Amps
Rated AC Voltage120/240 Volts
PhaseSingle phase
Rated Frequency60 Hertz
Normal Operating Range-20°F (-28.8°C) to 104°F (40°C)
Output Sound Level70 dB(A) at 23 ft. (7 m) at normal load