Essential Circuit Selection
When selecting the essential circuits that will be switched
to “Standby Power,” it is important that the sum of the
combined circuit loads does not exceed the wattage/
amperage capacity of the generator. To help you with your
selection of essential circuits, please consider the following:
Add up the total wattage of all electrical devices to be
connected at one time. This total should NOT be greater
than the generator’s wattage capacity.
The rated wattage of lights can be taken from light
bulbs. The rated wattage of tools, appliances and
motors can usually be found on a data plate or decal
affixed to the device.
If the appliance, tool or motor nameplate does not
list wattage, multiply volts times the ampere rating to
determine watts (Volts x Amps = Watts).
Some electric motors (induction types) require about
three times more watts of power for starting than for
running. This surge lasts for only a few seconds. Be
sure you allow for this high starting wattage when
selecting electrical devices that will be energized by the
home generator:
Figure the watts required to start the largest motor.
Add that to the total running watts of all other
connected loads.
This Briggs & Stratton home generator complies with the
following “stationary standby power rating”:
The standby power rating is applicable for supplying
power for the duration of normal power interruption.
No sustained overload capability is available for this
rating.
This rating is applicable to installations served by
a reliable normal utility source. This rating is only
applicable to variable loads with an average load factor
of 80% of the standby rating. The standby rating is
only applicable for optional standby power where the
generator set serves as the backup to the normal utility
source.
Use the wattage reference table provided and mark those
circuits you consider “critical” or “essential”. Make sure you
and your installer consider the system’s altitude above sea
level and the ambient temperature range when determining
total generator load.
IMPORTANT: When using the 100 Amp or 200 Amp transfer
switch with the home generator, you must turn off any non
essential loads. Failure to turn off non essential loads could
overload the generator causing it to shut down.
Some examples of non essential loads are as follows:
Pool pump
Hot tub
Electric hot tub and/or pool heaters
Central air conditioners
Electric hot water heaters
Electric range and/or oven
Arc welder
Non essential electric heaters
Delivery Inspection
Carefully inspect the home generator for any damage that
may have occurred during shipment.
IMPORTANT: If loss or damage is noted at time of delivery,
have the person(s) making delivery note all damage on the
freight bill and affix his signature under the consignor’s
memo of loss or damage. If loss or damage is noted after
delivery, separate the damaged materials and contact the
carrier and your installer for claim procedures. Missing or
damaged parts are not warranted.
The home generator is supplied with:
Home generator
Pre-attached mounting pad
One flexible hook-up hose (meets UL 569 and CSA 8.3)
Installation and Start-up manual
Operator’s manual
Installation checklist
Touch up paint
Oil drain tray
Roof hardware bag
One spare 15A fuse
2 Pole connector (for 240V from house)
10 Pole connector (for sensing and control wires)
Remote LED Indicator kit (red LED/plate/screws)
Required Items Supplied by Installer
Battery

Other manuals for Briggs & Stratton 10000 Watt

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Briggs & Stratton 10000 Watt and is the answer not in the manual?

Briggs & Stratton 10000 Watt Specifications

General IconGeneral
Rated Maximum Load Current at 120 Volts83.33 Amps
Rated Maximum Load Current at 240 Volts41.66 Amps
Rated AC Voltage120/240 Volts
PhaseSingle phase
Rated Frequency60 Hertz
Normal Operating Range-20°F (-28.8°C) to 104°F (40°C)
Output Sound Level70 dB(A) at 23 ft. (7 m) at normal load