ELECTRICAL DATA
Table 7 —24AHA4/124ANS Electrical Data
Unit Size --
voltage series
V/PH
OPER VOLTS* COMPRESSOR FAN
MCA
MAX FUSE**
or CKT BRK
AMPS
MAX MIN LRA RLA FLA
18-- 30
208/230/1 253 197
56.3 9.0 0.50 11.8 20
24-- 30 62.9 10.9 0.50 14.1 25
30-- 30 73.0 14.1 0.70 18.3 30
36-- 30 77.0 14.1 1.20 18.8 30
36-- 50 208/230/3 253 197 71.0 9.0 1.20 12.5 20
36-- 60 460/3 506 414 38.0 5.6 0.60 7.6 15
Table 8—25HHA4/224ANS Electrical Data
Unit Size --
voltage series
V/PH
OPER VOLTS* COMPRESSOR FAN
MCA
MAX FUSE**
or CKT BRK
AMPS
MAX MIN LRA RLA FLA
24-- 30
208/230/1 253 197
58.3 12.8 0.50 16.5 25
30-- 30 64.0 12.8 1.20 17.2 30
Table 9—40MKCB**B Electrical Data
Cooling Only Nominal
Indoor Size
Voltage
Voltage Range Fan Power
Min Max FLA Min Ckt Amps
Fuse H ACR Bkr
Amps
018, 022 208/230------1------60 187 253
0.485
1.0 15
028, 032 208/230------1------60 187 253
0.51
1.0 15
Table 10—40MKQB**B Electrical Data
Heat Pump Nominal
Indoor Size
Voltage
Voltage Range Fan Power
Min Max FLA Min Ckt Amps
Fuse H ACR Bkr
Amps
024, 028 208/230------1 ------60 187 253
0.51
1.0 15
*Permissible limits of the voltage range at which unit will operate satisfactorily.
LEGEND
FLA -- F u l l L o a d A m p s
HACR-- Heating, Air Conditioning, Refrigeration
LRA-- Locked Rotor Amps
NEC-- National Electrical Code
RLA--RatedLoadAmps(compressor)
*Permissible limits of the voltage range at which the unit will operate satisfactorily
**Time--Delay fuse.
Complies with 2007 requirements of ASHRAE Standards 90.1
NOTES:
1. In compliance with NEC requirements for multi-- motor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit
shall be fuse or equipped with a breaker.
2. Motor RLA valu es are established in acco rdance with UL ( Underwriters L aboratories) Standard 465.