5
LEGEND
*Air Conditioning & Refrigeration Institute.
NOTES:
1. Standard ratings are net values, reflecting the effects of circulating fan heat.
Supplementary electric heat is not included. Ratings are based on:
Cooling Standard:
80 F db, 67 F wb indoor entering-air temperature and
95 F db entering-air outdoor unit.
Hi-Temp Heating Standard:
70 F db indoor entering-air temperature and
47 F db/43 F wb entering-air outdoor unit.
Lo-Temp Heating Standard:
70 F db indoor entering-air temperature and
17 F wb/15 F db entering-air outdoor unit.
38AQS008, 012 and 40RMQ008, 012 are rated in accordance with ARI
Standard 210/240-94. 38AQS016 and 40RMQ016 are rated in accordance
with ARI Standard 340/360-93.
2. Sound ratings are in accordance with ARI Standard 270-84.
OUTDOOR
UNIT
38AQS
INDOOR
UNIT
40RMQ
AIRFLOW
(Cfm)
COOLING
HEATING
SOUND
RATING
(Bels)
Hi-Temp Low-Temp
Net Cap.
(Btuh)
EER IPLV
Net Cap.
(Btuh)
COP
Net Cap
(Btuh)
COP
008
008 3000 86,000 9.8 N/A 83,000 3.0 46,000 2.0 9.2
012
012 4000 108,000 8.9 11.2 111,000 3.0 62,000 2.0 8.8
016
016 6000 172,000 8.8 9.9 164,000 3.0 94,000 2.2 8.8
Bels
Sound Level (1 bel = 10 decibels)
COP
Coefficient of performance =
Btuh output
or
Btuh input
Btuh output
(Based on ARI conditions)
Unit Power Input x 3.413
EER
Energy Efficiency Ratio =
Btuh
(Based on ARI conditions)
Unit Power Input
IPLV
Integrated Part-Load Value
ARI* capacities

Questions and Answers: