EasyManuals Logo
Home>Carrier>Furnace>58MVP080

Carrier 58MVP080 User Manual

Carrier 58MVP080
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
The blower reduces its speed to low-heat RPM. The blower
and EAC remain operating 90, 135, 180, or 225 sec (depend-
ing on blower off time selection). The furnace is factory set for
a 90-sec blower off delay.
10. Post purgeThe inducer continues operating for 15 sec after
gas valve is de-energized.
Step 3Heating ModeTwo Stage
The control center provides 2-stage heating using a single-stage
thermostat. The control center maximizes comfort while optimiz-
ing efficiency to meet the demands of conditioned area when a
thermostat R-W/W1 signal is received.
If thermostat control over furnace staging is desired, a 2-stage
thermostat can be used. When control center receives a thermostat
R-W/W1 and R-W2 signal, high heat is energized and when a
R-W/W1 signal alone is received, low heat is energized. This
method overrides microprocessor control of high or low heat.
NOTE: When using 2-stage thermostat operation with R-W/W1
and R-W2 signals, setup switch SW-2 MUST be in ON position.
The heat cycle operates as stated in Heating Mode section.
To allow for greater comfort, 2-stage thermostat control is recom-
mended when zone systems are used.
Step 4Emergency Heat Mode
NOTE: The furnace should not be operated in emergency heat
mode for extended periods of time. Operation is only recom-
mended to provide heat until replacement components can be
obtained or fault resolved.
In this mode, the microprocessor is bypassed and motors operate at
full speed with high-heat operation. The heat exchangers, motors,
and electronics can be overstressed and may reduce the life of
components if operated for an extended period.
NOTE: No safeties are bypassed when using emergency heat
mode.
Emergency heat mode can be selected using setup switch SW-4.
SW-4 should be used when a fault condition exists or difficult to
resolve problems occur. This allows heating until fault can be
corrected.
In emergency heat mode, the normal heat mode outlined in
Heating Mode section is not followed. The following sequence
will occur:
When thermostat calls for heat, the R-W/W-1 circuits close.
1. Prepurge periodThe inducer motor is turned on IMMEDI-
ATELY operating at maximum speed, closing low- and
high-pressure switches. Prepurge begins 25 sec after high-
pressure switch closes.
2. Blower onThe blower motor is turned on IMMEDIATELY
and slowly increases to maximum speed as soon as a call for
heat is received. No blower calibration occurs.
3. Electronic Air CleanerThe EAC-1 terminal does not
operate in emergency heat mode.
4. HumidifierThe HUM terminal is energized IMMEDI-
ATELY.
5. Ignitor warm upThe HSI is energized for a 17 sec
warm-up period after prepurge period is completed.
6. Ignition sequenceAfter HSI warm-up period has com-
pleted, the gas valve is energized, permitting gas flow to
burners where it is ignited. After 5 sec, the HSI is de-
energized, and a 2-sec flame-sensing period begins.
NOTE: Emergency heat mode only operates in high heat.
7. Flame sensingWhen burner flame is sensed, control center
holds gas valve open. If burner flame is not sensed, control
center de-energizes gas valve and ignition sequence is re-
peated.
NOTE: Ignition sequence repeats 3 additional times before lock-
out occurs. Lockout automatically resets after 3 hr, or can be
manually reset by turning 115-v or 24-v power off (not at
thermostat) for 3 sec minimum, then turning on again. Fault codes
will not flash in emergency heat mode.
8. Blower off delayWhen thermostat is satisfied, the R-W/W1
signal is terminated, de-energizing gas valve (stopping gas
flow to burners), and HUM terminal is de-energized. The
blower stops immediately.
9. Post purgePost purge does NOT occur. The inducer stops
immediately.
Step 5Cooling Mode
SINGLE-SPEED APPLICATIONS
When thermostat calls for cooling, the R-G and R-Y/Y2 circuits
close.
1. Cooling unitThe cooling unit starts when thermostat R-Y
signal is received.
2. Blower onThe control center starts blower immediately
when it receives an R-Y/Y2 and R-G signal. The blower starts
at approximately 400-500 RPM. After 20 sec, the blower is
turned off for 1/10 of a sec where a coast down calibration is
done to evaluate resistance of the conditioned air duct system.
The microprocessor then determines blower RPM required to
provide selected cooling airflow.
NOTE: In cooling mode, the microprocessor adjusts blower RPM
to operate at 400 CFM per ton as selected on A/C setup switches.
Airflow will be reduced to 315 CFM per ton when a dehumidifi-
cation demand exists. See Air Conditioning Setup Switches
section. There is also a chart on wiring diagram. (See Fig. 24.)
NOTE: If Y/Y2 thermostat lead is not connected to furnace
control center, blower motor operates in continuous fan speed and
indoor coil freeze-up may occur.
3. Electronic Air CleanerThe EAC-1 terminal is energized
whenever blower operates.
4. Cooling unitThe cooling unit stops when thermostat R-Y
signal is terminated.
5. Blower off delayWhen thermostat is satisfied, the R-Y/Y2
and R-G signals are terminated, and blower remains operating
for 90 sec. The blower airflow will drop by 21 percent during
the off-delay period when the DE jumper is connected. The
DE jumper is only removed to enable the DEHUM input for
use with a thermidistat or humidistat for dehumidification
purposes.
TWO-SPEED APPLICATIONS
For details on 2-speed cooling applications, refer to Fig. 45.
Step 6Heat Pump Mode
SINGLE-SPEED APPLICATIONS
When furnace is operating in heat pump heating mode, R-Y/Y2
and R-G circuits are closed energizing heat pump, and blower
operates at cooling speed. When heat pump defrost is required,
R-W/W1 circuits close starting gas heat cycle, and blower adjusts
to low-heat speed.
1. Prepurge periodThe inducer motor is turned on and slowly
comes up to speed. When low-pressure switch closes, inducer
motor RPM is noted by microprocessor, and a 25 sec prepurge
period begins. The RPM is used to evaluate vent system
resistance. This evaluation is then used to determine required
RPM necessary to operate inducer in low-heat mode.
34

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 58MVP080 and is the answer not in the manual?

Carrier 58MVP080 Specifications

General IconGeneral
BrandCarrier
Model58MVP080
CategoryFurnace
LanguageEnglish

Related product manuals