Installing the AppController
AppController CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
11
4 Connect the binary output wiring to the screw terminals on the AppController and to the controlled device.
5 Insert the power screw terminal connector into the AppController's power terminals.
Wiring devices to the AppController's Rnet port
The Rnet communicates at a rate of 115 kbps and should be wired in a daisy-chain or hybrid configuration.
Supports up to
10 wireless and/or ZS sensors (5 per control program)
One Equipment Touch
One TruVu™ ET Display
NOTE ZS sensors, a Wireless Adapter, and an Equipment Touch can share the Rnet, but not SPT sensors.
Rnet wiring specifications
NOTE Use the specified type of wire and cable for maximum signal integrity.
4 conductor, shielded or unshielded, CMP, plenum rated cable
22 AWG (7x0096) bare copper if Rnet has only sensors
Low-smoke PVC (or equivalent)
If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire, terminated
at controller