Attaching a Chassis Ground Connection
Before You Begin
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority
or an electrician if you are uncertain that suitable grounding is available. Statement 1024
Warning
Before you connect power or turn on power to your chassis, you must provide an adequate chassis ground (earth) connection for the
chassis. A chassis ground connector is provided on each Cisco CBR-8 chassis.
The grounding wire is always the first to be installed or connected and the last to be removed or
disconnected.
Caution
Required Tools and Equipment
•
Phillips Screwdriver
•
¼-20 Phillips pan head with square cone lock washer (provided in accessory kit)
•
2 hole 4 AWG dual crimp compression lug (provided in accessory kit)
21