1.7 Auto Mode
• This mode can be selected with the remote controller
and the temperature setting can be adjusted between
16°C~30°C.
• In auto mode, the machine selects cooling, heating, or
fan-only mode on the basis of ∆T (∆T =T1-TS).
∆T Running mode
∆T>2°C(3.6°F) Cooling
-3℃(-5.4°F)≤∆T≤2°C(3.6°F) Fan-only
∆T<-3°C(-5.4°F) Heating*
Heating*: In auto mode, cooling only models run the fan
• Indoor fan will run at auto fan speed.
• The louver operates same as in relevant mode.
• If the machine switches mode between heating and
cooling, the compressor will keep stopping for certain
time and then choose mode according to ∆T.
1.8 Drying Mode
• In drying mode, AC operates the same as auto fan in
cooling mode.
• All protections are activated and operate the same as
they do that in cooling mode.
• Low Room Temperature Protection
If the room temperature is lower than 10°C, the
compressor ceases operations and does not resume until
room temperature exceeds 12°C.
1.9 Forced Operation Function
Press the AUTO/COOL button, the AC will run as below
sequence:
Forced auto →Forced cooling →Off
• Forced cooling mode:
The compressor and outdoor fan continue to run and
the indoor fan runs at breeze speed. After running for 30
minutes, the AC will switch to auto mode with a preset
temperature of 24°C(76°F).
• Forced auto mode:
Forced auto mode operates the same as normal auto mode
with a preset temperature of 24°C(76°F).
• The unit exits forced operation when it receives the
following signals:
• Switch off
• Changes in:
• mode
• fan speed
• sleep mode
• Follow me
1.10 Timer Function
• The timing range is 24 hours.
• Timer On. The machine turns on automatically at the
preset time.
• Timer Off. The machine turns off automatically at the
preset time.
• Timer On/Off. The machine turns on automatically at
the preset On Time, and then turns off automatically
at the preset Off Time.
• Timer Off/On. The machine turns on automatically at
the preset Off Time and then turns off automatically at
the preset On Time.
• The timer does not change the unit operation mode.
If the unit is off now, it does not start up immediately
after the “timer off” function is set. When the setting
time is reached, the timer LED switches off and the
unit running mode remains unchanged.
• The timer uses relative time, not clock time
1.11 ECO Function
• The ECO function is available in cooling, heating, or
auto mode.
• The operational process for sleep mode is as follows:
• When cooling, the temperature rises 1°C (to not
higher than 30°C) every hour. After 2 hours, the
temperature stops rising and the indoor fan is fixed
at low speed.
• When heating, the temperature decreases 1°C(to
not lower than 17°C) every hour. After 2 hours, the
temperature stops decreasing and the indoor fan is
fixed at low speed. Anti-cold wind function takes
priority.
• The operating time for sleep mode is 8 hours, after
which, the unit exits this mode and does not switches
off.
1.12 Auto-Restart function
• The indoor unit has an auto-restart module that
allows the unit to restart automatically. The module
automatically stores the current settings and in the
case of a sudden power failure, will restore those
setting automatically within 3 minutes after power
returns.