EasyManuals Logo
Home>CLIVET>Air Conditioner>MC2-Y 53M

CLIVET MC2-Y 53M User Manual

CLIVET MC2-Y 53M
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
Page 38
2.2 Centralized Controller
1) Connection
For Light commer
cial air conditioner with XYE port, it can be directly connected to Centralized Controller (CCM03, CCM09).
2) Address setting
When setting the address, please make sure the unit is powered off. The address can be set from 0 to 63 by the switch.
Turn on the unit, then the address will be effective.
Note: For light commercial aire conditioner with XYE port, it can be also connected to BMS (Building Management
System).
If there is any CAC (central air conditioner ) connecting with the central controller at the same time, please set the
address from largest (63,62,61…), since the CAC units could obtain address automatically from the smallest (00,01,02…)
Product Features

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET MC2-Y 53M and is the answer not in the manual?

CLIVET MC2-Y 53M Specifications

General IconGeneral
BrandCLIVET
ModelMC2-Y 53M
CategoryAir Conditioner
LanguageEnglish

Related product manuals