Installation
Page 45
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation according to the specifications
of the outdoor units.
Fasten the feet of this unit with bolts firmly to prevent it
from collapsing in case of earthquake or strong wind.
5. Drainage Pipe Installation
Install the drainage pipe as shown below and take
measures against condensation. Improperly installation
could lead to leakage and eventually wet furniture and
belongings.
5.1 Installation principle
Ensure at least 1/100 slope of the drainage pipe
Adopt suitable pipe diameter
Adopt nearby condensate water discharge
5.2 Key points of drainage water pipe
installation
1. Considering the pipeline route and elevation.
Before installing condensate water pipeline, deter-
mine its route and elevation to avoid intersection
with other pipelines and ensure slope is straight.
2. Drainage pipe selection
The drainage pipe diameter shall not small than the
drain hose of indoor unit
According to the water flowrate and drainage pipe
slope to choose the suitable pipe, the water flow-
rate is decided by the capacity of indoor unit.
Relationship between water flowrate and capacity of
indoor unit
Model
Water flowrate (l/h)
53M
4
According to the above table to calculate the total water
flowrate for the confluence pipe selection.
For horizontal drainage pipe (The following table is for
reference)
PVC
pipe
Reference
value of inner
diameter of
pipe (mm)
Allowable
maximum water
flowrate (l/h)
Remark
Slope
1/50
Slope
1/100
PVC25
20 39 27
For branch
pipe
PVC32
25 70 50
PVC40
31 125 88
Could be
used for
confluence
pipe
PVC50
40 247 175
PVC63
51 473
334
Attention: Adopt PVC40 or bigger pipe to be the main
pipe.