Specifications
Page 6
Condenser
Number of rows / 2
Tube pitch(a)x row pitch(b) mm 21x22
Fin spacing mm 1.3
Fin type (code) / Hydrophilic aluminum
Tube outside dia. and type mm
ɸ
7,Inner groove tube
Coil length x height x width mm 860x504x44
Number of circuits / 2
Outdoor side air flow(Hi) m3/h 2000
Outdoor sound pressure level dB(A) 55.5
Outdoor sound power level dB(A) 63
Throttle type Throttle type / EXV
Outdoor unit
Dimension(WxDxH) mm 800x333x554
Packing(WxDxH) mm 920x390x615
Net/Gross weight kg 33.7/36.6
Refrigerant
Refrigerant type / R32
GWP / 675
Refrigerant charge kg 1.15
Design pressure MPa 4.3/1.7
Refrigerant piping
Liquid side/ Gas side mm(inch)
ɸ
6.35/
ɸ
12.7(1/4”/1/2”)
Max. pipe length m 30
Max. difference in level m 20
Ambient temperature
Cooling
℃
-15~50
Heating
℃
-15~24
Qty’per 20’ /40’ /40’HQ Outdoor unit 108/219/292
Notes:
1) Capacities are based on the following conditions:
Cooling(T1): - Indoor Temperature 27°C(80.6°F) DB /19 °C(66.2°F) WB Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB
-Outdoor Temperature 35 °C(95°F) DB /24 °C(75.2°F) WB -Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB
-Interconnecting Piping Length 5m - Interconnecting Piping Length 5 m
- Level Difference of Zero. - Level Difference of Zero.
2) Capacities are Net Capacities.
3) Due to our policy of innovation some specifications may be changed without notification.