Data creazione 10/09/03 DS03I009GB--00 Pagina 13 di 59
INITIALISING THE MODULES
Each module configured and present in the Clivet Talk control system must be recognised by the local
network, which needs to know which device it is communicating with.
A series of basic rules must be observed when configuring the system, so as to avoid incorrect settings.
BASIC RULES FOR CONFIGURATION
Each module (central, evaporator, trio or tandem) will be identified by a network address, which must be set
using the corresponding dipswitches. The sequence of the addresses is not random, but rather must observe
the following rules.
• The address of the central module is always = 25
• The address of the local interface is always = 26
• The address of the remote interface is always = 27
• Modules with no address are not allowed
• The addresses of the modules that make up the same unit must be CONSECUTIVE.
• Each unit can only have one evaporator module (unit configurations are possible without an evaporator
module). The system can manage a maximum of 3 evaporator modules.
• Inside each unit, the addresses must be assigned considering the following sequence:
1. compressor module (trio or tandem)
2. evaporator module
3. In essence, the evaporator module must have the highest address inside each unit.
• Each unit can manage a maximum of 3 compressor modules (single, tandem or trio).
SETTING THE HARDWARE ADDRESS
The address of the modules must be set before any other configuration operation
• The local keypad and the remote keypad have no physical address set using the dipswitches
• The address of the central module is set using the combination of the dipswitches DIP2
• The address of the evaporator module is set using the combination of the dipswitches DIP1
• The address of the tandem module is set using the combination of the dipswitches DIP1
• The address of the trio module is set using the combination of the dipswitches DIP1