SET POINT CORRECTION IN HEATING
The current set point in heating is defined by the parameter SetHeat and by the following corrections:
• OutsideT correction
: value of the correction based on the outside temperature (between 0 and
MaxCextH).
• WR correction
: value of the Water Reset correction according to the external signal (between 0 and
MaxCWRH).
The current set point will therefore be defined as follows:
Current set point = SetHeat + OutsideT correction + WR correction
In any case, the value calculated in this way is automatically limited between the two values set for the
parameters MinSetH and MAXSetH, that is:
MinSetH > current set point < MAXSetH