EVAPORATOR MODULE ALARMS
Code displayed Reset Description-actions
E201 Evaporator inlet probe fault Automatic Disable load compensation and freecooling
E202 Evaporator outlet probe 1 fault Automatic Shut-down “UNIT-i” – pump on
E202 Evaporator outlet probe 2 probe
fault
Automatic Shut-down “UNIT-i” – pump on
E203 Programmable evaporator input
alarm
Automatic To be defined according to the associated
function
E204 Thermal cut-out alarm,
evaporator pump 1
Manual Shut-down “UNIT-i” – See pump
management
E205 Thermal cut-out alarm,
evaporator pump 2
Manual Shut-down “UNIT-i” – See pump
management
E206 Evaporator flow switch alarm Manual Shut-down “UNIT-i” – See pump
management
E207 Evaporator system fill alarm Manual Shut-down the entire SYSTEM – See pump
management
E208 Change pumps on evaporator Automatic See pump management
E209 Antifreeze alarm on evaporator Manual Shut-down “UNIT-i” – Pump on
E210 Tout 1, antifreeze pre-alarm on
evaporator
Automatic (*) Disable steps on UNIT-i (see example)
E211 Tout 2, antifreeze pre-alarm on
evaporator
Automatic (*) Disable steps on UNIT-i (see example)
E212 Pump system lockout Manual Total shut-down
E214 Disconnected module Automatic Total shut-down
NOTE
The evaporator module alarms have the same identifier on each evaporator module in the system.
Consequently, to correctly identify which module the fault refers to, see the associated code:
Example:
U2-EVAP (Alarm Evaporator Module 2)
E207 Evaporator system fill alarm
Indicates that the alarm condition is active on Evaporator Module 2