Troubleshooting Guide,
SW version IGS-NT-3.1.0, IM-NT-3.1.0, ©ComAp August 2018 27
IGS-NT Troubleshooting Guide.pdf
List of Possible Events
Hint:
Be aware that it is possible to change alarm messages using Translator in GenConfig. Try to find an
alarm text in the Trasnlator card if you can not find it on this list. Use Ctrl+F function to find an alarm
text.
Check PLC functions Force protect setting and customized protections (see card Protections in
GenConfig) to find alarm messages which are not listed below.
IGS-NT Alarm/History
record
Alarm/
History
Appeara
nce
Description
BIN 1-12
1
A+H
Indication of error in communication with binary inputs
extension module.
Check if the unit with corresponding CAN address is
- powered up
- address of the module is set correctly (see
Modules card in GenConfig and an extension
module manual)
- correctly connected and check connection of
terminating resistors on the CAN1 bus (see IGS-
NT Installation Guide, External modules
connection chapter)
- the CAN bus Low and High wires are not swapped
To check module communication activity look at the Tx
and Rx LEDs of the CAN bus port. Fast flashing means
that communication is OK.
ANA 1-10
1
A+H
Indication of error in communication with analog inputs
extension module.
Check if the unit with corresponding CAN address is
- powered up
- address of the module is set correctly (see
Modules card in GenConfig and an extension
module manual)
- correctly connected and check connection of
terminating resistors on the CAN1 bus (see IGS-
NT Installation Guide, External modules
connection chapter)
- the CAN bus Low and High wires are not swapped
To check module communication activity look at the Tx and
Rx LEDs of the CAN bus port. Fast flashing means that
communication is OK.
BOUT 1-12
1
A+H
Indication of error in communication with binary outputs
extension module.
Check if the unit with corresponding CAN address is
- powered up
- address of the module is set correctly (see
Modules card in GenConfig and an extension
module manual)
- correctly connected and check connection of
terminating resistors on the CAN1 bus (see IGS-
NT Installation Guide, External modules
connection chapter)
- the CAN bus Low and High wires are not swapped
To check module communication activity look at the Tx and
Rx LEDs of the CAN bus port. Fast flashing means that

Table of Contents