Troubleshooting Guide,
SW version IGS-NT-3.1.0, IM-NT-3.1.0, ©ComAp August 2018 7
IGS-NT Troubleshooting Guide.pdf
Unsuccessful controller programming
Procedure which is described in this chapter is part of the Boot Jumper Programming video which you
can watch here:
http://www.comap.cz/support/training/training-videos
It is necessary to use the boot jumper for controller programming in case of unsuccessful controller
firmware programming. It may for instance happen due to an accidental cable disconnection,
computer failure or remote connection drop out. If controller firmware programming was not
successful, it is not possible to open connection to a controller, it does not respond and controller
screen is blank. In such case you need to use this procedure for controller programming:
1. Close connection to controller and start GenConfig
2. Check communication port setting in GenConfig. Go to Options Select connection and select
the right communication port. It is necessary to use the RS232 (1) controller interface, boot jumper
programming does not work with the RS232 (2) or USB controller interface.
3. Go to File Firmware upgrade and Cloning… FW upgrade (default configuration)… and select
firmware you would like to upload into a controller.
4. Follow instructions in the notification window: