ENGLISH
80
Setting of the remote pressure sensor
PR Value Indication on display Full scale [bar] Fondo scala [psi]
0 Absent
1 Dab 16 bar 16 232
2 503 16 bar 16 232
3 501 R 25 bar 25 363
Table 19: Setting of the remote pressure sensor
The setpoint pressure is independent of the type of remote pressure sensor selected.
6.5.9 MS: Measurement system
This sets the measurement unit system; either international or Imperial The values displayed are shown in Table 20.
Units of measurement displayed
Value
International unit
of measurement
Imperial unit of
measurement
Restar
t
bar
p
si
Tem
p
erature °C °F
Table 20: Unit of measurement system
6.5.10 SX: Setpoint massimo
Sets the maximum value that any one of the setpoints SP, P1, P2, P3 can have (P2 and P3 are available only on type
MT and T/T inverters).
6.6 Technical Assistance Menu
From the main menu, press and hold “MODE” & “SET” & “+“ simultaneously until “TB” appears on display (or use the
buttons + or – in the selection menu). This menu enables the display and modification of various configuration
parameters. The MODE button enables the user to scroll through the menu pages, while buttons + and – enable
respectively to increase and decrease the value of the parameter concerned. To exit the current menu and return to
the main menu, press SET.
6.6.1 TB: Water failure block time
Entry of a water failure block delay time enables selection of the time (in seconds) taken by the inverter to notify of low
water levels on the electric pump.
Modifications to this parameter may be useful if a known delay exists between the moment in which the pump is
activated and the actual moment of supply. One example is that of a system where the electric pump intake line is
particularly long and is subject to small leaks. In this case it may occur that the pipeline empties, and even if the water
supply is regular, the electric pump takes some time to reload, deliver flow and pressurise the system.
6.6.2 T1: Shutdown time after low pressure signal
This sets the inverter shutdown time starting from reception of the low pressure signal (see Impostazione della
rilevazione di bassa pressione par. 6.6.15.5). The low pressure signal may be received on any of the 3 inputs, by
suitably configuring the input (Setup degli ingressi digitali ausiliari IN1, IN2, IN3 par. 6.6.15).
T1 can be set between 0 and 12 s. The default setting is 2 s.
6.6.3 T2: Shutdown delay
This sets the delay after which the inverter shuts down after shutdown conditions have been reached: system
pressure and flow at minimum values.
T2 can be set between 2 and 120 s. The default setting is 10 s.
6.6.4 GP: Proportional gain coefficient
The proportional gain should generally be increased for elastic systems (wide and PVC pipelines) and reduced in the
case of rigid systems (narrow and steel pipelines).
To maintain constant system pressure, the inverter performs a PI check on the measured pressure error. On the basis
of this error, the inverter calculates the power to supply to the electric pump. The behaviour of this check depends on
the set parameters GP and GI. To meet the different requirements of the various types of hydraulic systems where the
system may operate, the inverter enables the selection of parameters that are different from the default settings. On
virtually all systems, the factory setting of parameters GP and GI are optimal. However, in the event of problems
with regulation, these settings may be modified as required.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DAB ACTIVE DRIVER PLUS T/T 3 and is the answer not in the manual?

DAB ACTIVE DRIVER PLUS T/T 3 Specifications

General IconGeneral
BrandDAB
ModelACTIVE DRIVER PLUS T/T 3
CategoryInverter
LanguageEnglish

Related product manuals