EasyManuals Logo

Daikin 3MXS24RMVJUA User Manual

Daikin 3MXS24RMVJUA
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #214 background imageLoading...
Page #214 background image
Troubleshooting for Outdoor Unit SiUS121736EA
201 Service Diagnosis
7.16 CT or Related Abnormality
Error Code H8
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 h 5 h
Method of Error
Detection
A CT or related error is detected by checking the compressor running frequency and CT-detected
input current.
Error Decision
Conditions
The compressor running frequency is more than A Hz and input current is less than B A.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective power module
Broken or disconnected wiring
Defective reactor
Defective outdoor unit PCB
A (Hz) B (A)
18/24 class 32 0.5
36 class 55 0.5

Table of Contents

Other manuals for Daikin 3MXS24RMVJUA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 3MXS24RMVJUA and is the answer not in the manual?

Daikin 3MXS24RMVJUA Specifications

General IconGeneral
BrandDaikin
Model3MXS24RMVJUA
CategoryAir Conditioner
LanguageEnglish

Related product manuals